press alarm
key for record
Maintenance man
password
0000
Change of hours of operation
Fan
Compress 1
Compress 2
Limit of hours of
operation
(x1000)
Fan
99 Comp1 99
Humidify
99 Comp2 99
Sensor offset
Humidity
_ _ _ %
Transducer
_ _ _ bar
Pressure2
_ _ _ bar
Sensor offset
Ambient temp.
00:0°C
External temp.
00:0°C
Delivery temp.
00:0°C
Sensor offset
Condens. temp.
_ _ _ °C
Cond. temp.2
_ _ _ °C
Manual procedure
Digit. output 01
Off
Digit. output 02
Off
Digit. output 03
Off
Manual procedure
Digit. output 04
Off
Digit. output 05
Off
HED-HCAT SE FREE COOLING
Press the alarm warning key to display all the stored
A4
alarms displayed in the time period.
Range H001-H999
Select the password with the scrolling selectors to access
A5
the menu for setting the maintenance parameters.
Factory value 123
Range 0+9999
The mask A6 can be used to change the hours of opera-
A6
tion of the delivery fan, compressor 1 and compressor 2.
Factory value 0
Range 0÷99 . 0÷999
Unit of measurement Hours.
The mask A7 can be used to change the thresholds of the
A7
hours of operation of the devices.
Factory value 99
Range 0÷99
Unit of measurement Hours x 100
The display page A8 can be used to calibrate the pressure
A8
sensor.
Factory value 0
The display page A9 can be used to calibrate the sensor:
A8
ambient temperature, external temperature and delivery
temperature.
Factory value 0
Range –9.9÷9.9
Unit of measurement °C
The mask Aa can be used to calibrate the condensation
Aa
temperature sensor 1 and the condensation temperature
sensor 2.
Factory value0
Range -9,9 ÷ 9,9
Unit of measurement °C
The mask Ab is used for manual activation of the digital
Ab
outputs 1-2-3.
Factory value Off.
Range Off ÷ On
The mask Ac is used for manual activation of the digital
Ac
outputs 4-5.
Factory value Off.
Range Off ÷ On