Lonworks points of PAHCMR000 (Return air temperature control)
n AHU Control/Monitor point
No.
Name
1 ON/OFF (Setting)
2 ON/OFF (Status)
3 Operation Mode (Setting) SNVT_hvac_mode nviHeatCool
4 Operation Mode (Status) SNVT_hvac_mode nvoHeatCool
5 Lock (Setting)
6 Lock (Status)
7 Set Temperature (Setting) SNVT_temp_p nviSetPoint
8 Set Temperature (Status) SNVT_temp_p nvoSetPoint
1)
9 Fan Speed (Setting)
1)
10 Fan Speed (Status)
11 Mode Lock (Setting)
12 Mode Lock (Status)
13 Fan Speed Lock (Setting) SNVT_switch
14 Fan Speed Lock (Status)
15 Temperature Lock (Setting)
16 Temperature Lock (Status) SNVT_switch
17 Temperature Lower limit (Setting) SNVT_temp_p nviLow_HW_Tmp input °C(16~30 °C)
18 Temperature Lower limit (Status)
19 Temperature Higher limit (Setting) SNVT_temp_p nviUp_Tmp
20 Temperature Higher limit (Status) SNVT_temp_p nvoUp_Sol_Tmp output °C(18~30 °C)
21 Product Type
22 Product Address
23 Room Temperature
24 Error Code
NOTE
• ACP Lonworks gateway is required for Lonworks protocol.
• In case of PAHCMS000, Lonworks protocol is not supported.
• For more details, refer to the manual of control product.
- For fan speed control, it is necessary to set DIP SW 1-3 'ON'.
Network
Object Type
Variable
SNVT_switch
nviOnOff
SNVT_switch
nvoOnOff
SNVT_switch
nviLock
SNVT_switch
nvoLock
SNVT_switch
nviFanSpeedCmd
SNVT_switch
nvoFanSpeed output
SNVT_switch
nviModlok
SNVT_switch
nvoModlok
nviFanlok
SNVT_switch
nvoFanlok
SNVT_switch
nviTmplok_Humid input 0.0 0 (OFF) 100.0 1 (ON)
nvoTmplok_Humid output 0.0 0 (OFF) 100.0 1 (ON)
SNVT_temp_p nvoLow_HW_Tmp output °C(16~30 °C)
SNVT_count
nvoPType
SNVT_count
nvoPAddr
SNVT_temp_p nvoSpaveTemp output 0~255
SNVT_hvac_status nvoUnitStatus output mode/0/0/0/0/0/alarm
Object
Type
input 0.0 0 (OFF) 100.0 1 (ON)
output 0.0 0 (OFF) 100.0 1 (ON)
input
HVAC_HEAT HVAC_COOL HVAC_FAN_ONLY
output
HVAC_HEAT HVAC_COOL HVAC_FAN_ONLY
input 0.0 0 (OFF) 100.0 1 (ON)
output 0.0 0 (OFF) 100.0 1 (ON)
input °C(18~30 °C)
output °C(18~30 °C)
input
1.00(Low) 2.00(Med) 3.00(High)
1.00(Low) 2.00(Med) 3.00(High)
input 0.0 0 (OFF) 100.0 1 (ON)
output 0.0 0 (OFF) 100.0 1 (ON)
input 0.0 0 (OFF) 100.0 1 (ON)
output 0.0 0 (OFF) 100.0 1 (ON)
input °C(18~30 °C)
output 0
output 0~255
BMS PROTOCOL
37
Unit