n UI7(Analog Input) – ODU Capacity Control #1
<3 System>
Each ODU's capacity ratio [%]
Total
Voltage
Capacity
ODU
[V]
ratio [%]
Master#1
0
0.0
2.0
26.7
40
2.5
30.0
50
3.0
33.3
60
3.5
36.7
70
4.0
40.0
40
4.5
46.7
40
5.0
50.0
50
5.5
56.7
50
6.0
60.0
60
6.5
66.7
60
7.0
70.0
70
7.5
76.7
70
8.0
80.0
80
8.5
86.7
80
9.0
90.0
90
9.5
96.7
90
10.0
100.0
100
NOTE
• ODU Capacity ratios mentioned in the table above are not exact.
• 'Evaporative temperature / Condenser temperature' may vary depending on system operating
frequency, pressure option setting and piping installation conditions.
• Single Split ODU is only supporting <1 system> table.
CAUTION
!
Actual temperature at evaporator may varies by pressure drop. Please contact local sale
person to design AHU heat exchanger.
DISCHARGE AIR TEMPERATURE CONTROL (PAHCMS000)
ODU
ODU
Master#2
Master#3
Operation OFF
0
40
0
40
0
40
0
40
40
40
50
50
50
50
60
60
60
60
70
70
70
70
80
80
80
80
90
90
90
90
100
100
100
100
<4 System>
Each ODU's capacity ratio [%]
Total
Voltage
Capacity
ODU
[V]
ratio [%]
Master#1
0
0.0
2.0
20.0
40
2.5
22.5
50
3.0
25.0
60
3.5
27.5
70
4.0
40.0
40
4.5
47.5
40
5.0
50.0
50
5.5
57.5
50
6.0
60.0
60
6.5
67.5
60
7.0
70.0
70
7.5
77.5
70
8.0
80.0
80
8.5
87.5
80
9.0
90.0
90
9.5
97.5
90
10.0
100.0
100
27
ODU
ODU
ODU
Master#2
Master#3
Master#4
Operation OFF
0
40
0
0
40
0
0
40
0
0
40
0
40
40
40
50
50
50
50
50
50
60
60
60
60
60
60
70
70
70
70
70
70
80
80
80
80
80
80
90
90
90
90
90
90
100
100
100
100
100
100

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pahcms000

Table of Contents