DISCHARGE AIR TEMPERATURE CONTROL (PAHCMS000)
26
n UI7(Analog Input) – ODU Capacity Control #1
'ODU Capacity Control #1' is available when DIP SW2-1 is OFF, each Master ODU will have a different
operating ratio according to following tables.
<1 System >
ODU Capacity
Voltage (V)
Range (%)
0.0
Operation OFF
4.0
40
4.5
40
5.0
50
5.5
50
6.0
60
6.5
60
7.0
70
7.5
70
8.0
80
8.5
80
9.0
90
9.5
90
10.0
100
NOTE
• Based on 7.5 m piping length condition, According to piping length evaporating/condensing
temperature will be increasing/decreasing.
• ODU Capacity ratios mentioned in the table above are not exact.
• 'Evaporative temperature / Condenser temperature' may vary depending on system operating
frequency, pressure option setting and piping installation conditions.
• Single Split ODU is only supporting <1 system> table.
CAUTION
!
The actual temperature at the evaporator may vary by pressure drop. Please contact a local
sale person to design an AHU heat exchanger.
Estimated
Estimated
Eva. Temp.
Cond. Temp.
(Te,°C)
(Tc,°C)
-
-
14.0
33.5
14.0
33.5
12.0
36.5
12.0
36.5
10.5
39.0
10.5
39.0
9.0
41.5
9.0
41.5
8.0
44.0
8.0
44.0
7.0
46.5
7.0
46.5
6.0
49.0
<Main Module>
<2 System>
Total
Voltage
Capacity
[V]
ratio [%]
ODU Master#1 ODU Master#2
0
0
2.0
20.0
2.5
25.0
3.0
30.0
3.5
35.0
4.0
40.0
4.5
45.0
5.0
50.0
5.5
55.0
6.0
60.0
6.5
65.0
7.0
70.0
7.5
75.0
8.0
80.0
8.5
85.0
9.0
90.0
9.5
95.0
10.0
100.0
100
Each ODU's capacity
ratio [%]
Operation OFF
40
0
50
0
60
0
70
0
40
40
40
50
50
50
50
60
60
60
60
70
70
70
70
80
80
80
80
90
90
90
90
100
100