Digital Input - External Power Source (12 V DC)
Name
Port
ON/OFF
DI1 - DCOM
Cool/Heat
DI2 - DCOM
Emer. Stop
DI3 - DCOM
DI Control
+12 V-DCOM
CAUTION
!
Please check the electrical specification of digital output (DO) of DDC controller whether
12 V DC or non-voltage for 'DI Control'. According to the electrical spec. of DO of DDC
controller, 'DI Control' should be set. If the wrong setting is made, DI does not work
properly.
n Digital Output (Relay C contact)
Name
Port
Alarm
DO1
n Digital Output
Name
Port
ON/OFF
DO2
Defrost
DO3 Defrost Normal
Comp. Status
DO4
Reserved
DO5
Reserved
DO6
DISCHARGE AIR TEMPERATURE CONTROL (PAHCMS000)
Value
Short
Open
ON
Heating
Cooling
Emergency
Normal
Stop
Internal Power
External Power
Source
Source
Value
Electrical Spec.
- Normal Status
A
B
COM
30 V DC / 1 A
- Error Status
250 V AC / 1 A
A
B COM
Value
Electrical Spec.
Short
Open
ON
OFF
250 V AC / 1 A
ON
OFF
30 V DC / 1 A
-
-
-
-
*DI is available when DIP SW1-1 is OFF
Electrical Spec.
OFF
12 V DC 10 mA Operation ON/OFF
12 V DC 10 mA Operation Mode
12 V DC 10 mA
Non voltage
Output normal or error status
(Relay C Contact)
- A Contact
Normal status : open
Error status : short
- B Contact
Normal status : short
Error status : open
Operation ON/OFF status
ODU Defrost status
Compressor operation ON/OFF status
Function
Emergency Stop Input (Priority
operation)
Use external power source for DI
+12 V-DCOM should be "Open"
Function
Function
-
-
25