n Outdoor unit Monitor point
No.
Name
1
Compressor Operation Status outdoor_CompOperStatus_XX
3
Inverter Fan 1 frequency
4
High Pressure
5
Low Pressure
6
Suction Temperature
7
Liquid Pipe Temperature
8
Heat Exchanger Temperature outdoor_HexTemp_XX
9
Outdoor EEV
10
Subcool EEV
11
Hot Gas Valve
12
Inverter Discharge Temperature outdoor_InverterDischargeTemp_XX
13
Outdoor Temperature
14
Operation Mode
NOTE
• ACP BACnet gateway is required for BACnet protocol.
• In case of PAHCMS000, BACnet protocol is not supported.
• For more details, refer to the manual of control product.
Object Name
Object
(XX : Unit Address
Number)
outdoor_InverterFanFreq_XX
outdoor_HighPressure_XX
outdoor_LowPressure_XX
outdoor_SunctionTemp_XX
outdoor_LiquidPipeTemp_XX
outdoor_OutdoorEEV_XX
outdoor_SubCoolEEV_XX
outdoor_HotgasValue_XX
outdoor_OutdoorTemp_XX
outdoor_OperationMode_XX
Inactive
Type
TEXT-0 TEXT-1 TEXT-2 TEXT-3 TEXT-4 TEXT-5
BI
Stop(0)
Run(1)
AI
-
AI
-
AI
-
AI
°C
AI
°C
AI
°C
AI
-
AI
-
BI
Stop(0)
Run(1)
AI
°C
AI
°C
MI
STOP(1) COOL(2) HEAT(3)
Unit
Active