PHASE 3
Cut-over Fire Panel Lines to New CDS-9090 device.
NOTE: Leave it unmarked or place a "2" or an "S" on its phone cord.
d. If cable runs coming from the Fire Panel terminate in the Telco closet demarc/SIN to
a 66 or 110 block, check the following:
- Determine which jack is associated with the Primary or Secondary line of Fire Panel and
mark them accordingly it if not already apparent/visible.
- Isolate the Telco side connection from those two (2) pairs (i.e. lift bridging clips on
66-Block) Punch-down the two pairs of the new cable run to a dual SMT jack or two (2)
Single-port SMT jacks (a.k.a. biscuit jacks)
- Determine and mark/label each SMT jack cover with its new device Telephone number
plus some primary or secondary suffix - i.e: 678.555.1234 678.555.2468 FIRE PNL-Prim
FIRE PNL-Sec
2. Mount the SMT Jack(s) somewhat near to the DataRemote CDS-9090 device depending on 5' long
phone cord's reach and distance between 66-Blk & SMT box(es)
3. Using your cable tester, test both SMT jack terminations and take PHOTO of test results to add to
deliverables (REQUIRED).
4. Using included phone cords with RJ-11 terminations, connect FXS alarm ports from CDS-9090
device to the "FIRE-Primary & FIRE-Secondary" SMT box respectively
5. Mark Cables:
- Mark the DataRemote CDS-9090 device alarm line 1 port's phone cord with a "1" or "P"
to reflect it connects to the DataRemote CDS-9090 device's alarm line 1 port.
- Mark the DataRemote CDS-9090 device's alarm 2 port's phone cord with a "2" or "S" to
reflect it connects to the DataRemote CDS-9090 device's alarm line 2 port.
PHASE 4
Testing Fire Alarm communication over
DataRemote's CDS-9090 device.
The DataRemote CDS-9090 device will be set in auto alarm mode. Meaning it will detect what type
of supported protocol the panel communicates in (Contact-ID, SIA, Pulse...Etc)
NOTE: do not plug in a butt set to the cds-9090 device and make a test call on any of the alarm
lines as this will deactivate the auto detect mode.
The first call will fail, if calls continue to fail contact installation support.
(continued)