Alpha-InnoTec Luxtronik Operating Manual page 37

Heating and heat pump controller part 2
Hide thumbs Also See for Luxtronik:
Table of Contents

Advertisement

No.
Display
760
Defrosting fault
761
LIN timeout
762
sensor evaporator intake
763
sensor compressor intake
764
Sensor compressor heater
765
Overheating
766
compressor's functional
range
767
STB E-Rod
768
Flow monitoring
769
Pump control
770
Low superheat
771
High superheat
776
limit of application-CP
777
Expansion valve
778
Low pressure sensor
779
High pressure sensor
780
EVI sensor
781
Liquid temp. sensor before
EXV
782
Suction gas EVI temp.
sensor
783
Communication SEC
board – Inverter
784
VSS lockdown
785
SEC-Board defective
786
Communication SEC
board – Inverter
787
VD alert
788
Major VSS fault
789
LIN/Encoding not found
790
Major VSS fault
We reserve the right to make technical changes | 83055400fUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
Description
Defrosting ended 5 times in succession by maximum time
(strong wind impinges on evaporator) .
LIN timeout.
Tü sensor error (evaporator intake).
Tü1 sensor error (compressor intake).
Sensor error compressor heater.
Overheating longer than 5 minutes below 2K.
Operation for 5 minutes outside the compressor's functional
range.
STB of the heating element has been activated.
Insufficient flow in defrost cycle.
After 10 sec compressor runtime excessively low flow.
Overheating lies below the limit value for a lengthy period.
Overheating lies below the limit value for a lengthy period.
Compressor operates outside its use limits for a lengthy
period.
Expansion valve is defective.
Low-pressure sensor is defective.
High-pressure sensor is defective.
EVI sensor is defective.
Liquid temperature sensor upstream of the ex-valve is
defective.
Suction gas EVI temperature sensor is defective.
Communication between the SEC board and the inverter is
disrupted.
Inverter is blocked.
Error found in the SEC board.
Fault found in communication between the SEC and
HeatingIO of the SEC board.
Compressor signals faults.
Fault in the inverter.
Control unit unable to find coding. Either the LIN
connection is interrupted or the coding resistor is not
detected.
Fault in the power supply of the inverter / compressor.
Remedy
Protect the fan and evaporator from strong
wind.
Check cable/contact.
Check sensor, replace if necessary.
Check sensor, replace if necessary.
Check sensor, replace if necessary.
When switching on for the first time, check
rotary field, otherwise phone customer
service.
Check rotary field.
Check the heating element and press the
fuse back in.
Check hydraulics, check pump, check flow.
Check PWM cable, check pump.
Check the temperature sensor, pressure
sensor and expansion valve.
Check the temperature sensor, pressure
sensor, fill quantity and expansion valve.
Check the thermodynamics.
Check the expansion valve, connection
cable and if applicable the SEC board.
Check the sensor, connector and
connection cable.
Check the sensor, connector and
connection cable.
Check the sensor, connector and
connection cable.
Check the sensor, connector and
connection cable.
Check the sensor, connector and
connection cable.
Check the connection cable, interference
suppression capacitors and wiring.
Disconnect the complete system from the
power supply for 2 minutes.
If it occurs again, check the inverter and
compressor.
Replace the SEC board.
Check the Heating/IO SEC board cable
connection.
Acknowledge fault.
If an error occurs repeatedly, phone the
authorised service personnel (customer
service).
Check the inverter.
Check the connection cable LIN / coding
resistor.
Check the wiring, inverter and
compressor.
37