Alpha-InnoTec Luxtronik Operating Manual page 21

Heating and heat pump controller part 2
Hide thumbs Also See for Luxtronik:
Table of Contents

Advertisement

NOTE
Connect domestic hot water thermostat on the same ter-
minals as the domestic hot water sensor (low voltage). The
domestic hot water thermostat must be suitable for low
voltage (floating contact).
Thermostat closed (= signal On) = Domestic hot water re-
quirement.
Service water 2
Domestic Hot Water 2
CP
Setting CP means circulation pump.
 For the corresponding settings, please refer to the description
of the circulation pump in the operating manual intended for
end customers, found in program section "Domestic hot wa-
ter" under the section entitled "Circulation".
h.wCP
Setting h.w.CP means that the CP
output will be active during domestic
hot water preparation and switch off
30 seconds after domestic hot water
preparation is complete.
Service water 3
Domestic Hot Water 3
with CP
Additional circulation pump runs
during domestic hot water preparation
no CP
Additional circulation pump does
not run during domestic hot water
preparation
Service water 4
Domestic Hot Water 4
set value
Heat pump attempts to reach the set
setpoint value of the domestic hot
water temperature
Service water 5
Domestic Hot Water 5
with HSP
Heating circulation pump runs always
during domestic hot water preparation
no HSP
Heating circulation pump does not run
during domestic hot water preparation
par HUP
Heating recirculation pump operates
parallel with domestic hot water
preparation if a heating requirement
exists. If the heating limit is exceeded,
the heating circulation pump switches
off.
SW+HP max
Maximum running time domestic hot
water preparation + Heat pump
After the set time has expired, the 2nd heat generator in the
domestic hot water preparation energises, but only if this has
been released previously in the heating mode!
Defr cycle max
Defrost cycle time, maximum time
between two defrost processes
You can find the time to be set for the relevant L/W device in
the operating instructions. If you do not find any data there,
the following applies:
 page 40, "Overview: Defrost cycle, Air defrost, Flow Max"
Defrost. Air
Air defrost
No
Air defrost not released
Yes
Air defrost generally released above
the set temperature
We reserve the right to make technical changes | 83055400fUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
 Approved appliances, see page 40, "Overview: Defrost cy-
cle, Air defrost, Flow Max"
ATTENTION
Do not set an "air defrost" on non-approved appliances.
Defr.Air max
Maximum duration of air defrost
Defrost 2
Option only possible for L/W devices with 2 compressors
with 1CP
Defrost with only one compressor
with 2CP
Defrost with two compressors, if these
also supply before defrosting
Pump opt.
Pump optimisation
No
Heating circulation pumps always
run, unless another supply type is
requested (domestic hot water, ...) or
the device is switched off
Yes
Setting only effective with an outdoor
temperature > 0 °C.
Heating circulation pumps are
switched off, if required
The heating circulation pumps will
be switched if the heat pump has
not been requested for more than 3
hours. The heating circulation pumps
will then cycle for 5 minutes every 30
minutes until the heat pump receives
another request.
If the external temperature is above
the return setpoint temperature, the
heating circulation pumps will be
switched off permanently. They will
be switched on for 1 minute every 150
hours to prevent them from becoming
stuck
ATTENTION
For multi-functional domestic hot water tank integration
with solids or solar, pump optimisation must be set to "No".
Access
Data access authorisation
The "Fitter" (= Qualified technicians) provides access to
parameters without a password, which otherwise requires
"Customer service" access.
Brine pres/Flow
Brine pressure / flow
No
neither brine pressure pressostat nor
flow switch connected
Brine pres
for S/W devices, a brine pressure
pressostat is connected on the Defr/
Brin/Flow input
Flow
for W/W devices, a flow switch is
connected on the Defr/Brin/Flow input
Pow.suppl.
Phase monitoring relay installed in
the supply pipe of the compressor is
connected on Defr/Brin/Flow input
Pow.+Flow
Phase monitoring relay and flow switch
are connected on the Defr/Brin/Flow
input
21