OPERATING CONDITIONS & REQUIREMENTS
APPLICATION LIMITATIONS PF-OXY:
 pH: for Iron removal: 6,8 - 9,0
for Manganese removal: 8,0 - 9,0
for Iron & Manganese removal: 8,0 - 8,5
 maximum contaminant content:
Iron (Fe
Manganese (Mn
Hydrogen Sulfide (H
 organic matter: max. 4,0 mg/L; higher level may hinder the correct operation of
the system.
 chlorine: max. 1,0 mg/L
 iron bacteria: if iron bacteria are present, frequent service may be necessary,
while the life of the system may be limited; by properly controlling the iron
bacteria with chlorine or another approved method of bacterial reduction, the
system will function properly.
APPLICATION LIMITATIONS PF-OXY
 pH: 5,8 - 10,5
 maximum contaminant content:
Iron (Fe
Manganese (Mn
Hydrogen Sulfide (H
 organic matter: water should be free from organic matter.
 iron bacteria: if iron bacteria are present, frequent service may be necessary,
while the life of the system may be limited; by properly controlling the iron
bacteria with chlorine or another approved method of bacterial reduction, the
system will function properly.
OPERATING PRESSURE MIN-MAX: 2,5-8,0 bar / 36-116 psi
 low operating pressure may lead to insufficient backwash of the filter media,
resulting in an increase in pressure drop and/or a reduction of the filtration
capacity during the service cycle.
 if installed on a well, verify that the well pump is powerful enough to provide
sufficient flow rate for the backwash cycle.
 check water pressure regularly.
 take into account that night time water pressure may be considerably higher than
day time water pressure.
 install a pressure reducer ahead of the appliance if necessary.
OPERATING TEMPERATURE MIN-MAX: 4-48 °C / 39-120 °F
 do not install the appliance in an environment where high ambient temperatures
(e.g. unvented boiler house) or freezing temperatures can occur.
 the appliance cannot be exposed to outdoor elements, such as direct sunlight or
atmospheric precipitation.
 do not install the appliance too close to a water heater; keep at least 3 m (10 ft)
of piping between the outlet of the appliance and the inlet of the water heater;
2+
)
2+
)
S)
2
+
2+
)
2+
)
S)
2
Page 5
15 mg/L
2 mg/L
5 mg/L
:
70 mg/L
35 mg/L
15 mg/L
EN - English