Clogged Filter Detector; Smoke Detector; High Temperature Safety Thermostat; Remote Fault Relay - Trane RT-SVX19A-E4 Installation Operation & Maintenance

Rooftop units
Table of Contents

Advertisement

Clogged filter detector

This device is mounted in the filter
section. The sensor measures the
difference in pressure before and
after the filter section. The
information is sent to the THP03
thermostat, to a Tracker™ or to a
BMS.

Smoke detector

This device is used to detect smoke
in the air stream. It includes a
factory mounted detector connected
to a central panel, both fitted in the
fan section.
When smoke is detected, it shuts off
the unit. A dry contact is available
on the control panel for a remote
default.
Table 32 - Thermostats features
non-programmable
programmable
electronic
unit control type design
interface card needed
for Cooling Only units
for Heat Pump units
for Gas Fired units
Cooling stages
auxiliary heating stages
(elec. heater, HWC )
heating stages
(heat pump mode)
liquid crystal display
*some important features are lost while using the CTI card.
Note: thermostats are powered up by the rooftop control (24V)
38
Controls
High temperature safety
thermostat
This additional safety device is a
manual reset thermostat for gas
fired units (YKD/YKH), required
mainly by the French ERP
regulation. It is located in the gas
burner section. It stops the gas
burner and the supply air fan when
the supply air temperature rises to
120°C.

Remote fault relay

This is a factory mounted relay used
to send alarm signals (dry contact)
to a local BMS or a local control
panel. With this relay, the
compressor, heating, fan and power
supply alarm output signals from
the controller are reported to a
single dry contact.
THS01
THP01
X
-
-
X
X
X
electromech.
electromech.
CTI*
CTI*
X
X
-
-
X
X
2
2
2
2
none
none
X
X

Thermostats

6 thermostats are available:
THS01/THP01, THS02/THP02 and
THS03/THP03.
"THS" are non programmable
thermostats, "THP" are
programmable.
01 and 02 series are conventional
thermostat, 03 series are dedicated
to the controller.
THS02
THP02
X
-
-
X
X
X
electromech.
electromech.
CTI*
CTI*
-
-
X
X
-
-
2
2
1
1
1
1
X
X
THS03
THP03
X
-
-
X
X
X
Reliatel
Reliatel
none
none
X
X
X
X
X
X
2
2
2
2
1
1
-
X
RT-SVX19A-E4

Hide quick links:

Advertisement

Table of Contents
loading