Filter Installation - Trane RT-SVX19A-E4 Installation Operation & Maintenance

Rooftop units
Table of Contents

Advertisement

14
Installation

Filter installation

To gain access to filters, remove the
supply fan access panel on
downflow units and the filter access
panel on the end for horizontal
units.
Each unit ships with 40 or 50 mm
thick filters. Number and size of
filters is determined by size and
configuration of the unit.
Table 5 - Filter arrangement
UNIT
YKH/YKD 155
YKH/YKD 175
YKH 200
YKD 200
YKH 250
YKD 250
TKH/TKD 155
TKH/TKD 175
TKH 200
TKD 200
TKH 250
TKD 250
WKH/WKD 125
WKH/WKD 155
WKH 200
WKD 200
CAUTION! Do not operate unit
without filters in place.
The maximum pressure drops
allowable on filters are:
EU2/G2: 120 Pa
EU4/G4: 150 Pa
EU2/G2
Qty
Size
2
(508x508x50)
4
(508x635x50)
2
(508x508x50)
4
(508x635x50)
8
(508x635x50)
4
(508x508x50)
4
(508x635x50)
8
(508x635x50)
4
(508x508x50)
4
(508x635x50)
2
(508x508x50)
4
(508x635x50)
2
(508x508x50)
4
(508x635x50)
8
(508x635x50)
4
(508x508x50)
4
(508x635x50)
8
(508x635x50)
4
(508x508x50)
4
(508x635x50)
2
(508x508x50)
4
(508x635x50)
2
(508x508x50)
4
(508x635x50)
8
(508x635x50)
4
(508x508x50)
4
(508x635x50)
EU4/G4
Qty
Size
2
(498x498x40)
4
(500x625x50)
2
(498x498x40)
4
(500x625x50)
8
(500x625x50)
4
(498x498x40)
4
(500x625x50)
8
(500x625x50)
4
(498x498x40)
4
(500x625x50)
2
(498x498x40)
4
(500x625x50)
2
(498x498x40)
4
(500x625x50)
8
(500x625x50)
4
(498x498x40)
4
(500x625x50)
8
(500x625x50)
4
(498x498x40)
4
(500x625x50)
2
(498x498x40)
4
(500x625x50)
2
(498x498x40)
4
(500x625x50)
8
(500x625x50)
4
(498x498x40)
4
(500x625x50)
RT-SVX19A-E4