Side-Load Filters

Filters are also available with a side access rack.

2-inch or 4-inch Flat Side-Load Filters

1. Disconnect the power to the unit.
2. Open the filter section access door and remove the
filters and block-offs from their installed position.
3. Slide the filter into the rack.
4. Some side load racks will be provided with block-off
plates.
5. Close and secure the door, making certain the door
closes snug against the block-off.
Figure 36. Filter block-off placement
Figure 37.
Hood installation
Detail A
AHU outdoor roof
Butyl caulk tape
1.00 W x .125T
Nut-Hex .31-18
Bolt .313-18 x .750 Hex
Bracket Support
Angle Hood Support
(when required)
CLCH-SVX010A-EN
Butyl caulk tape
1.00 W x .125T
Hood
Nut-Hex .31-18
Bolt .313-18 x .750 Hex
Component Installation Requirements

Bag or Cartridge Side-Load Filters

1. Disconnect power to the unit.
2. Keeping the bag filters folded, slide each filter into the
filter rack, pushing them tightly against the unit. Pleats
should be in the vertical position.
3. If using optional pre-filters, slide them into the
appropriate filter rack.
4. If block-offs are provided with the unit, slide the block-
offs into the filter track.
5. Close and secure the access door, making certain the
door closes snug against the rack.
Note: The block-off is intended to make a seal when the
access door is closed. It may require a few
adjustments to ensure a proper seal.

Magnahelic Air Filter Gage

Check zero adjustment of the gage. Turn both vent valves
to the "Vent" position and adjust the gage pointer to zero
by means of the external adjustment screw in the face of
the gage. After zeroing, turn the vent valves to the "Line"
position.

Outdoor Unit Weather Hood(s)

1. Per the unit drawing determine mounting location of
the unit weather hoods.
2. Using the factory provided screws mount the weather
hoods to the unit.
3. On larger units, weather hoods may be large enough to
require angled down supports. In those cases, the
angles are shipped attached to the hood but will need
to be connected to the air handler by the installing
contractor.
Note: It is required that the hoods be sealed to the unit
using field provided caulk or gasket.
Screw self-driller
1/4-in. x .750
33