Trane TSC060-120 User Manual page 24

Packaged cooling with electric heat rooftop units 50 hz
Table of Contents

Advertisement

Table PD-11 — Belt Drive Evaporator Fan Performance -TSC090AD - Horizontal Configuration (SI)
25
50
m
3
/h
RPM
kW
RPM
kW
1.50 Nom kW Std Motor & Low Static Drive
4080
-
-
673
0.42
4590
702
0.51
738
0.56
5100
771
0.68
805
0.74
5610
842
0.89
873
0.96
6120
913
1.14
942
1.22
1.50 Nom kW Standard Motor & Drive
External Static Pressure (Pascals)
275
300
CFM
RPM
kW
RPM
kW
1.50 Nom kW Standard Motor & Hi Static Drive
4080
1035
1.04
1070
1.12
4590
1073
1.22
1104
1.31
5100
1117
1.44
1146
1.53
5610
1165
1.72
1194
1.80
6120
1215
2.04
1242
2.13
2.24 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Table PD-11a — Belt Drive Evaporator Fan Performance -TSC090AD - Horizontal Configuration (IP)
.10
.20
CFM
RPM
BHP
RPM
BHP
2 HP Std Motor & Low Static Drive
2400
-
-
673
0.56
2700
702
0.68
738
0.76
3000
771
0.91
805
1.00
3300
842
1.19
873
1.29
3600
913
1.53
942
1.63
2 HP Standard Motor & Drive
External Static Pressure (Inches of Water)
1.10
1.20
CFM
RPM
BHP
RPM
BHP
2 HP Standard Motor & Hi Static Drive
2400
1035
1.39
1070
1.50
2700
1073
1.64
1104
1.76
3000
1117
1.93
1146
2.05
3300
1165
2.30
1194
2.41
3600
1215
2.73
1242
2.86
3 HP Over-Sized Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
24
Performance
Data
External Static Pressure (Pascals)
75
100
RPM
kW
RPM
kW
RPM
718
0.47
769
0.54
814
773
0.62
817
0.68
862
837
0.81
870
0.87
912
903
1.03
930
1.10
963
970
1.30
996
1.37
1021
325
350
RPM
kW
RPM
kW
RPM
1104
1.19
1137
1.27
1168
1136
1.40
1167
1.48
1198
1176
1.62
1205
1.72
1233
1220
1.88
1248
1.98
1275
1269
2.22
1295
2.31
1319
External Static Pressure (Inches of Water)
.30
.40
RPM
BHP
RPM
BHP
RPM
718
0.63
769
0.72
814
773
0.83
817
0.92
862
837
1.08
870
1.17
912
903
1.38
930
1.47
963
970
1.74
996
1.84
1021
1.30
1.40
RPM
BHP
RPM
BHP
RPM
1104
1.60
1137
1.70
1168
1136
1.87
1167
1.99
1198
1176
2.17
1205
2.31
1233
1220
2.52
1248
2.66
1275
1269
2.98
1295
3.10
1319
125
150
175
kW
RPM
kW
RPM
1.50 Nom kW Standard Motor & Drive
0.61
855
0.67
893
0.76
904
0.85
941
0.94
951
1.03
989
1.17
1000
1.25
1037
1.45
1052
1.52
1086
1.50 Nom kW Standard Motor &
Hi Static Drive
375
kW
1.35
1.57
1.82
2.08
2.40
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product's Warranty Will Not Be Affected.
.50
.60
.70
BHP
RPM
BHP
RPM
2 HP Standard Motor & Drive
0.82
855
0.90
893
1.02
904
1.13
941
1.26
951
1.38
989
1.57
1000
1.68
1037
1.94
1052
2.04
1086
2 HP Std Motor & Hi Static Drive
1.50
BHP
1.81
2.11
2.44
2.79
3.22
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product's Warranty Will Not Be Affected.
200
225
kW
RPM
kW
RPM
kW
0.73
929
0.81
965
0.88
0.92
975
0.98
1009 1.06
1.12
1025
1.21
1056 1.28
1.34
1073
1.45
1106 1.55
1.61
1121
1.71
1153 1.82
2.24 Nom kW OS
Motor & Hi Static Drive
.80
.90
BHP
RPM
BHP
RPM BHP
0.98
929
1.08
965
1.18
1.23
975
1.32
1009 1.42
1.51
1025
1.62
1056 1.72
1.80
1073
1.94
1106 2.08
2.16
1121
2.29
1153 2.44
3 HP Over-Sized Motor
& Hi Static Drive
RT-PRC016-EN
250
RPM
kW
999
0.96
1041 1.14
1088 1.36
1136 1.63
1184 1.93
1.00
RPM BHP
999
1.29
1041 1.52
1088 1.82
1136 2.19
1184 2.59

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents