Table PD-10 — Belt Drive Evaporator Fan Performance -TSC090AD - Downflow Configuration (SI)
25
50
3
m
/h
RPM
kW
RPM
kW
1.50 Nom kW Standard Motor & Low Static Drive
4080
-
-
-
-
4590
-
-
-
-
5100
-
-
703
0.61
5610
713
0.69
755
0.77
6120
771
0.88
809
0.96
External Static Pressure (Pascals)
275
300
CFM
RPM
kW
RPM
kW
1.50 Nom kW Std Motor
& Drive
4080
980
0.95
1013
1.02
4590
1010
1.11
1043
1.19
5100
1045
1.31
1076
1.39
5610
1081
1.54
1111
1.63
6120
1116
1.79
1148
1.89
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Table PD-10a — Belt Drive Evaporator Fan Performance -TSC090AD - Downflow Configuration (IP)
.10
.20
CFM
RPM
BHP
RPM
BHP
2 HP Standard Motor & Low Static Drive
2400
-
-
-
-
2700
-
-
-
-
3000
-
-
703
0.81
3300
713
0.93
755
1.03
3600
771
1.19
809
1.29
External Static Pressure (Inches of Water)
1.10
1.20
CFM
RPM
BHP
RPM
BHP
2 HP Standard Mtr
& Drive
2400
980
1.27
1013
1.37
2700
1010
1.49
1043
1.60
3000
1045
1.76
1076
1.87
3300
1081
2.06
1111
2.18
3600
1116
2.39
1148
2.53
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
RT-PRC016-EN
Performance
Data
75
100
RPM
kW
RPM
kW
-
-
701
0.47
699
0.53
743
0.59
747
0.68
789
0.74
797
0.85
836
0.92
848
1.06
885
1.14
325
350
RPM
kW
RPM
kW
1.50 Nom kW Standard Motor
& Hi Static Drive
1046
1.10
1076
1.17
1074
1.27
1105
1.36
1105
1.47
1134
1.56
1141
1.72
1168
1.80
1177
1.99
1204
2.08
2.24 Nom kW Over-Sized Motor
& Hi Static Drive
External Static Pressure (Inches of Water)
.30
.40
RPM
BHP
RPM
BHP
-
-
701
0.63
699
0.70
743
0.79
747
0.91
789
0.99
797
1.15
836
1.24
848
1.42
885
1.53
1.30
1.40
RPM
BHP
RPM
BHP
2 HP Standard Motor &
Hi Static Drive
1046
1.47
1076
1.57
1074
1.71
1105
1.82
1105
1.98
1134
2.09
1141
2.30
1168
2.42
1177
2.66
1204
2.79
3 HP Over-Sized Mtr & Hi Static Drive
External Static Pressure (Pascals)
125
150
RPM
kW
RPM
kW
RPM
1.50 Nom kW Standard Motor & Drive
750
0.54
794
0.60
787
0.66
830
0.74
827
0.82
867
0.90
873
1.00
908
1.08
921
1.22
954
1.30
375
RPM
kW
1106
1.25
1134
1.44
1163
1.65
1197
1.90
1232
2.18
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product's Warranty Will Not Be Affected.
.50
.60
RPM
BHP
RPM
BHP
2 HP Standard Motor & Drive
750
0.72
794
0.81
787
0.89
830
0.99
827
1.10
867
1.20
873
1.34
908
1.45
921
1.63
954
1.74
1.50
RPM
BHP
1106
1.68
1134
1.93
1163
2.21
1197
2.55
1232
2.93
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product's Warranty Will Not Be Affected.
175
200
225
kW
RPM
kW
RPM
834
0.67
873
0.73
909
871
0.82
908
0.89
943
906
0.98
944
1.06
980
944
1.17
980
1.26
1016 1.35
986
1.39
1019
1.49
1052 1.58
1.50 Nom kW Standard Motor
& Hi Static Drive
.70
.80
.90
RPM
BHP
RPM
BHP
RPM BHP
834
0.90
873
0.98
909
871
1.09
908
1.19
943
906
1.31
944
1.43
980
944
1.57
980
1.69
1016 1.82
986
1.87
1019
1.99
1052 2.13
2 HP Standard Motor
& Hi Static Drive
250
kW
RPM
kW
0.80
945
0.87
0.96
977
1.04
1.15
1013 1.23
1050 1.45
1085 1.69
1.00
RPM BHP
1.08
945
1.17
1.29
977
1.39
1.54
1013 1.65
1050 1.94
1085 2.26
23