Temperature probes (NTC10k)
Pb1 (P1C = NTC): 13-14
Pb2 (P2C =NTC): 13-15
Temperature probes (NTC10k, PT1000, NTC86k)
Pb3 (P3C = NTC, PT1000, NTC86k): 19-21
Pb4 (P4C = NTC, PT1000, NTC86k): 19-20
Ratiometric transducers (0.5÷4.5Vdc)
Pb1 (P1C = 0-5)
13 (+); 14(in); 16 (gnd)
Pb2 (P2C =0-5)
13 (+); 15(in); 16 (gnd)

4.4 DIGITAL INPUTS

D.I.1: available if probe P3 in not available (P3P=no)
D.I.2: always available
D.I.3: available if probe P4 in not available (P4P=no)
NOTE: all digital inputs are free of voltage input types

4.5 ANALOGUE OUTPUT: OAN

Output PWM: 17(-); 18(+)
Output 0-10Vdc: 17(+); 18(-)

4.6 POWER OUTPUT: OA3 (TRIAC)

There are 2 different models, characterized by a different TRIAC power supply stage. As
general rule, the TRIAC is always internally connected to the device power supply line.
1592001530 XC15-35CX EN r1.2 11.04.2017