Analogue output:
-
-
-
-
-
-
bEn
Buzzer enabled: n; Y

15.16 DIGITAL INPUTS

Digital inputs 1 and 3 depend on the presence of probe P3 and P4 respectively. Digital input 2 is
always available.
ixF
Digital input function (x=1, 2, 3):
nu=not used
Enb=enabling regulation signal
LP=external low pressure alarm
HP=external high pressure alarm
ES=energy saving mode activation and deactivation
SiL=silent mode activation and deactivation
EAL=external alarm (warning)
bAL=external alarm (lockout)
oAx=output oAx (x=1, 2, 3, n) deactivation
rEV=inversion for analogue output (oAn=PrP)
ixP
Digital input polarity (x=1, 2, 3)
oP = active when contact is open
CL = active when contact is closed
dxd
Activation delay for digital input (x=i, 2, 3): 0 to 255 min
nPx
Max number of external alarm events, detected from a digital input, before
stopping the regulation (x=1, 2, 3): (0 to 15) if ixF=LP, HP or bAL, after detecting
nPx alarms in an interval of time diA, the regulation will be stopped.
diA
Interval of time for LP, HP, bAL lockout alarm management: 0 to 100 hours.
When diA=0 this function is disabled.
HPF
Minimum time with compressor locked in case of LP, HP, bAL lockout alarms:
0 to 15 min
Ar
Regulation restart in case of any lockout alarm: MAn=manual, a power-off and
power-on is required; Aut=automatic after resetting the alarm condition

15.17 OTHER

Adr
Serial address: 1 to 247
Hur
Real Time Clock: 0 to 23 hours
Min
Real Time Clock: 0 to 59 min
dAY
Real Time Clock: Sun to Sat, day of the week
Hd1
First holiday of the week: Sun to Sat
Hd2
Second holiday of the week: Sun to Sat
iLE
Start time for silent mode on workdays: (0.0 to 24h00min, res. 10 min) when the
silent mode is active the maximum speed of ventilators will be set to the value of
par. FSS.
dLE
Silent mode duration on workdays: 0.0 to 23h50min, res. 10 min
iSE
Start time for silent mode on holidays: (0.0 to 24h00min, res. 10 min) when the
silent mode is active the maximum speed of ventilators will be set to the value of
par. FSS.
dSE
Silent mode duration on holidays: 0.0 to 23h50min, res. 10 min
1592001530 XC15-35CX EN r1.2 11.04.2017
nu=output not used
onF=output activated when controller in ON
ALr=alarm output
EFn=electronic ventilator control
PrP=analogue repeater
inV=inverter-controlled compressor output