SLC 5/03 (OS30x), SLC 5/04 (OS40x) and SLC 5/05 (OS50x) Firmware History
OS302, Series C, FRN 8
OS401, Series C, FRN 8
OS501, Series C, FRN 8
released: May 2004
OS501, Series C, FRN 9
released: November 2004
Publication 1747-RM001G-EN-P - November 2008
Enhancements
None
Enhancements
Only SLC 5/05 Series C processor hardware can support
IMPORTANT
100 Mbps Ethernet and increased Ethernet connections.
Updating processor hardware Series A and B to OS501,
Series C, FRN 9 does not increase either the Ethernet port
speed or the number of available Ethernet connections on
the processors.
• Enable/Disable HTTP (Web) Server
Using RSLogix 500 V6.30 and higher, you can disable the SLC 5/05
HTTP web server functionality from within the Channel 1
Configuration by unchecking the HTTP Server Enable check box
shown in Figure A.1.
Figure A.1 Channel 1 System Configuration Defaults
SNMP Server Enable
HTTP Server Enable
The default (checked HTTP Server Enable box shown in Figure A.1)
allows you to connect to the SLC 5/05 using a web browser. Although
this parameter can be downloaded to the processor as part of a program
download or changed and applied while online with the processor, a
processor power cycle is required in order for the change to take affect.