Siemens Climatix Series Short Manual page 19

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Prerequisites
Parameterization
Parameter
Pres.ctrd tmp
Pres.setp.clg
Pres.setp.htg
Pres.sasetp.clg
Pres.sasetp.htg
External setpoint
Supply air comp.
Comfort heating
Comfort dead zone
Setp.extra sequ.
Setp.min sply.temp
Setp.max sply.temp
Setp.min sply.temp
Setp.max sply.temp
Delta flt.maxlim.
Delta flt.minlim.
Fan htng deadz
Short Manual for Climatix Control System [v. 2.14.10, 2.14.20, 2.14.30 & 2.14.40]
SMCX.130215.02GB
2.7.2
Temperature setpoints
Displays only functions that are enabled in Configuration 1 or Configuration 2. All
other functions are hidden.
Main menu > Unit > Temp. control > Temp. setpoints
Value
---
---
---
---
---
---
-10.0...10.0 [°C]
0...99 [°C]
0...20 [°C]
0...99 [°C]
15.0... Setp.max
supply temp [°C]
Setp.min supply
temp ... 50.0 [°C]
-64.0 ...99.0 [°C]
-64.0 ...99.0 [°C]
0.0...64.0 [°C]
0.0...64.0 [°C]
0...20 [°C]
Function
Present temperature used for control.
Either supply air, room air or extract air temperature,
depending on setting and control type.
Present calculated room or supply air setpoint for cooling.
Present calculated room or supply air setpoint for heating.
Present calculated supply air setpoint for cooling using
cascade control.
Present calculated supply air setpoint for heating using
cascade control.
Present external setpoint or setpoint compensation.
Setpoint compensation for winter operation for:
Tmp control mode = RmSplyC Su (Room supply air cascade
control in summer, pure supply air control in winter).
or
Tmp control mode = RtSplyC Su (return supply air cascade
control in summer, pure supply air control in winter).
The room setpoint for cascade control, active in the
summer, are active (summer - winter changeover).
During winter, these room setpoints must be adapted to
the supply air control.
Comfort based setpoint for heating. Only available when
Tmp stpt selection = +/-Half Dz.
Comfort dead zone. Only available when Tmp stpt
selection = Clg - degrees Celsius or Htg + degrees Celsius
or +/- Half Dz.
Setpoint for extra heating, extra electric heating, extra
cooling if configured as stand alone.
Lowest permissible supply air temperature for pure room
or extract air control with additional available supply air
sensor. Limited control of the cooling setpoint occurs if the
supply air temperature < Setp.min sply.temp. The heating
register is started if this is not enough.
Highest permissible supply air temperature for pure room
or extract air control with additional available supply air
sensor. Limited control of the heating setpoint occurs if the
supply air temperature > Setp.max sply.temp.
Lowest permissible supply air temperature for cascade
control.
Highest permissible supply air temperature for cascade
control.
Maximum difference between supply air and room air
temperature for heating when Floating Min/Max is enabled
(Configuration 2).
Maximum difference between supply air and room air
temperature for cooling when Floating Min/Max is enabled
(Configuration 2).
Controller dead zone: Setpoint = Supply air heating
setpoint – dead zone.
Page 17