LED keypad programming

This section describes how to program the address of each LED keypad, as well
as the options that are available. The keypad must be addressed for control
panel supervision of that keypad. Programming defaults include:
Four-digit master code: 1, 2, 3, 4.
Six-digit master code: 1, 2, 3, 4, 5, 6.
Four-digit go to program code: 9, 7, 1, 3.
Six-digit go to program code: 9, 7, 1, 3, 0, 0.
To assign the keypad's LEDs to start at a zone other than one:
1. Enter *, 9, 2, program code.
2. Enter the starting zone number (1 to 16).
3. Press * to save and exit.

Keypad options

To program the keypad options:
1. Enter *, 9, 3, program code.
2. The Service LED begins flashing. You can now toggle LEDs 1 to 8 on/off to
enable/disable the functions shown in Table 4 below.
3. Press * after enabling/disabling the desired functions.
Table 4: LED 1 to 8 functions
LED
1
2
3
4
5
6
7
NX-8E Control Panel Installation Manual
Keypad feature enabled
Reserved. Do not program this LED.
Enable silent keypad option. Silences the entry/exit sounder and chime
only.
Enable ding dong sound for chime. If off, chime is a single tone.
Enable keypress silence option. Silences the pulsing keypad s ounder
for 5 seconds when a key is pressed.
Enable armed status suppression. Will not allow the keypad to display
faulted or bypassed zones when the system is armed.
Enable panic, fire, emergency beep tone. Sounds a short beep to verify
that the keypress was accepted.
Suppress the Service LED. Will not allow the Service LED to light for
any reason. If there is a system problem, pressing *2, shows the service
menu.