1. CD332 Overview

1.1 Introduction

The change detect DC input module CD332 (hereafter called CD332) is an 8 points 12
- 24 Vdc input module with interrupt generation function for Toshiba's Programmable
Controller PROSEC-T3 or T3H (hereafter called T3 generically).
When the input signal status of the CD332 is changed, the CD332 generates an
interrupt for the T3. Then the T3 immediately stops ordinary operation and starts to
execute the pre-assigned I/O interrupt program.
The task switching time in the T3 is less than 500 µs. (under interrupt enable state)
The interrupt generation timing of the CD332 can be selected as follows for each input
point. This selection is made by the DIP switches provided on the front of the CD332.
(1) Rising edge (from OFF to ON)
(2) Falling edge (from ON to OFF)
(3) Both edges (both OFF to ON and ON to OFF)
This CD332 has 8 input points. By using one CD332, up to 8 interrupt factors can be
processed. On the other hand, up to 8 I/O interrupt programs are available in the T3.
Therefore, total up to 64 (= 8 × 8) interrupt factors can be processed by the T3 by using
8 CD332s.
The input voltage of the CD332 is 12 to 24 Vdc. The input delay time can be selected
either normal or high speed as 8 points block by setting the internal jumper plugs.