GE 1200 Series Interconnection And Wiring Manual page 32

Fire panels, repeaters, and emulators
Table of Contents

Advertisement

1200-2000 Series Fire Panels, Repeaters, and Emulators
32
Interconnection and Wiring Guide
Standard inputs
Input
Sounder board
FEP board (FP2xxx
and FB2x00 only)
FP1216 only; FP1200 optional SD1200 card used.
1
SD2000 card.
2
3
FP2xxx only - SD2000 card used.
Power supply requirements
Input
Output
Supervisory
Fuses
Maximum current
drawn from the
primary input
Maximum output
ripple voltage
Fault Relay
(Configuration
depends on jumper
setting.)
FP/FR12xx / FR2000
1
4 x supervised inputs (1-4)
3.3 kOhm termination
FP/FR12xx & FR2000
230 VAC (+10%, -15%)
50 Hz (±10%)
50 VA
21 – 28 VDC
24 V standby battery
Aux. Power: 19-27.5
VDC, 100 mA (max)
Modem: 5 VDC (±0.1V),
75mA (max)
Battery charge: 27.6
VDC (±0.2 V) @ 25 °C,
300 mA (max)
- Mains fail
- Battery disconnect
- Battery flat
- Flat battery cut-out
- Earth fault
- Auxiliary supply fault
Mains:
T 0.8A 250V
250 mA
± 300 mV
Maximum switching
current: 2A @ 24VDC
Maximum power
rating: 50 W
FP1216EN / FP1264 / FP12xxN
4 x supervised inputs (1-4)
3.3 kOhm termination
FP1216EN & FP1264
FP/FR2xxx / FP2xxxN
230 VAC (+10%, -15%)
230 VAC (±15%)
50 Hz (±10%)
50 Hz (±10%)
220 VA
200 VA
21 – 28 VDC
21 – 28 VDC
24 V standby battery
24 V standby battery
Aux. Power: 19-27.5
Auxiliary Voltage:
VDC, 100 mA (max)
20.5-28 V
Modem: 5 VDC (±0.1V),
27.6V DC battery
75mA (max)
charge voltage, 4A
total (battery charge
Battery charge:
and aux. with or
27.6 VDC (±0.2 V) @ 25
without batteries.)
°C, 1.6 A (max)
- Mains fail
- Mains fail
- Battery disconnect
- Battery disconnect
- Battery flat
- Battery flat
- Flat battery cut-out
- Flat battery cut-out
- Earth fault
- Auxiliary supply fault
Mains:
Mains:
T 2A 250V
T 2A 250V
Battery / AUX output:
T 5A
1 A
1 A
± 300 mV
± 300 mV
Maximum switching
-
current: 2A @ 24VDC
Maximum power
rating: 50 W
2
FP/FR2xxx
3
4 x supervised inputs (1-4)
3.3 kOhm termination
4 x auxiliary inputs
15 VAC or 20-28 VDC
3 mA
FR2032/20128
FR2064/20255
21 – 28 VDC
24 V standby battery
- Mains fail
- Charger fail
Mains:
T 1A 250V
0.3 A (no options
installed)
-

Advertisement

Table of Contents
loading