Control sequence
modulating output
Notes:
22 / 46
Siemens
Smart Infrastructure
The diagram below shows the control sequence of a continuous PI control.
Heating and cooling mode (P01 = 4 or 3)
Heating mode with manual selection
(P01=2)
This function (4-pipe modulating) is only available with RDF340 (2 analog outputs
DC 0...10 V are required).
· The diagrams only show the PI thermostat's proportional part.
· For the fan sequence see section 4.8.
RDF300... / RDF340... / RDF400... / RDF600... Basic Documentation
T[°C]
Room temperature
w
Room temperature setpoint
V1
Control command "Valve" Heating
V2
Control command "Valve" Cooling
XpH
Proportional band "Heating"
XpC
Proportional band "Cooling"
X
Dead zone
dz
Cooling mode with manual selection
(P1=2)
CE1P3076.en