Siemens RDF300 Series Basic Documentation page 32

Flush-mounted room thermostats for fan coils, with lcd
Hide thumbs Also See for RDF300 Series:
Table of Contents

Advertisement

Adjust parameters
Reset parameters
Note! *)
Control parameters
#
Parameter
Service Level
P01
Control sequence
P02
Mode selection via user operating mode button
P04
Selection of °C or °F
P05
Sensor calibration
P06
Standard temperature display
P07
Additional user info
P08
Comfort basic setpoint
P09
Minimum setpoint limitation for Comfort
(WminComf)
P10
Maximum setpoint limitation for Comfort
(WmaxComf)
P11
Heating setpoint for Economy
P12
Cooling setpoint for Economy
P13
Electrical reheater for cooling mode
P14
Key lock
(Press the operating mode button
to enable or disable the key lock) RDF600... : 3
seconds
Note
32 / 46
Siemens
Smart Infrastructure
3. Select the required parameter by repeatedly pressing buttons + and -.
4. When you press buttons + and - simultaneously, the current value of the
selected parameter starts to flash, which can be changed by repeatedly
pressing buttons + or -.
5. When you again press buttons + and – simultaneously, the next parameter is
displayed.
6. Repeat Steps 3 to 5 to display and change additional parameters.
7. All changes are saved and the controller returns to Protection 10 seconds after
the last display or setting.
The factory settings for the control parameters can be reloaded via parameter P71,
by changing the value to "ON", and confirming by pressing buttons + and –
simultaneously. The display shows "8888" during reload.
· RDF400... and RDF600T: Step 1 is not required.
· RDF3... and RDF600: Step 1 is required.
If one of the digital inputs is commissioned as window contact, and the contact is
closed, the controller will be switched to ECO mode and parameter setting will
not be possible. Solution: open the window contact.
(WheatEco)
(WcoolEco)
for 7 seconds
· P02 is not available when the controller is commissioned for manual
heating/cooling changeover P01=2
· Parameter display depends on selected application and function
(x) Not available
RDF300... / RDF340... / RDF400... / RDF600... Basic Documentation
Factory
Setting range
setting
2-pipe:
[0..3]
0:= Heating only
1 (Cool only)
1:= Cooling only
2:= Manual H/C
4-pipe:
[2...4]
3:= Auto changeover
4 (Heat&Cool)
4:= Heating & cooling
1 (Stb, Comf)
1 = Stb,Comf
2 = Stb, Comf, Eco
°C (0)
(0) °C or
(1) °F
0.0 K
– 3 ... +3 K
0 (Room temp)
0:= Room temperature
1:= Setpoint
0 (no display)
0:= no display
1:= Temp in °C and °F
21 °C
5 ... 40 °C
5 °C
5 ... 40 °C
35 °C
5 ... 40 °C
15 °C
OFF, 5 °C...WcoolEco
30 °C
OFF, WheatEco...40 °C
ON
ON:= enabled
OFF:= disabled
0 (Unlocked)
0:= Unlocked
1:= Auto lock
2:= Manual lock
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
r
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
CE1P3076.en