Instructions for installation and use

13.0 Adjustment and commissioning, DHW Cylinder circuit

Domestic hot water
The VX Solo II substations types HWP and HWS are supplied with
connection pipes for domestic hot water cylinder on the primary
or secondary side.
The temperature in the DHW cylinder can be controlled by the
Danfoss ECL controller in combination with an actuator + valve.
Danfoss ECL Comfort 210/310
The application Key contains information about application, language
and factory settings, adapted to the type of system, for which it is
ordered.
Note! Various applications can be loaded.
The controller is factory-set for local language and the running time
for the actuator (DHW circuit) is preset for the actual application.
General controller settings such as "Time and Date" must be entered
during commissioning of the controller. And also the desired DHW
temperature must be set.
(Make sure that the immersion sensor is placed correctly before mak-
ing adjustment of the temperature).
Please refer to the enclosed manufacturer instructions for the ECL
210/310 controller in order to set the required domestic hot water
temperature in the DHW cylinder circuit:
ECL Application Key Box with ECL Comfort 210/310 user guide and
mounting guide, for further information.
We recommend that your order commissioning of the controller with
your local Danfoss Sales Company.
Below schedule states whether the VX Solo II is supplied with
connection pipes for DHW cylinder on the primary side or the se-
condary side, and whether the DHW temperature in the cylinder is
controlled by the electronic controller and also states the controller
application and the actuator/valve combination.
Type
VX Solo II HWP
(ECL 210/A237), page 6
VX Solo II HWP
(ECL 210/A247), page 7
VX Solo II H2WP
(ECL 210/A260), page 8
VX Solo II H2WP
(ECL 310/A377), page 9
VX Solo II HWS
(ECL 210/A237), page 10
VX Solo II HWS
(ECL 210/A247), page 11
VX Solo II H2WS
(ECL 210/A267), page 12
Please note:
Circulation pump for the domestic hot water on the secondary side of
the cylinder is not part of the delivery and must be mounted on site.
Supply limit
VX Solo II with primary
connection for cylinder
Danfoss District Energy
Primary Connection for Cylinder
Control not part of delivery
Danfoss ECL 210, Application A247
+ AHQM / AMV 150
Control not part of delivery
Danfoss ECL 310, Application A377
+ AHQM / AMV 150
VX Solo II substations
Secondary Connection for Cylinder Pump for Cylinder Circuit
Danfoss ECL 210, Application A237
(AHQM / AMV 13)
Danfoss ECL 210, Application A247
(AHQM / AMV 150)
Danfoss ECL 210, Application A267
(AHQM / AMV 13)
VI.GP.P2.02
Grundfos UPS 15-40
Grundfos UPS 15-40
Grundfos UPS 15-40
Supply limit
VX Solo II with secondary
connection for cylinder
DKDHR
31 31