11. Enter 30 and then the monitoring station account numbers and telephone numbers of the telephone lines
being used. The following screens for telephone Line 1 will appear,
Enter 4-6 digit ID#
Account ID: _ _ _ _ _ _
Press <#> when done
or <*> to cancel.
Enter 31 to input the area code (prefix code) of telephone line 1. The following screen will appear,
First digits to dial
Prefix Code: _ _ _
Press <#> when done
or <*> to cancel.
Enter 32 to input the telephone number of line 1. The following screen will appear,
Local number to dial
Telephone #: _ _ _ _ _ _ _
Press <#> when done
or <*> to cancel.
Repeat step 11 for the second telephone line by entering Item numbers 40 and 41.
12. Set the Format to be generated by the UDACT when reporting to the monitoring station for both telephone lines.
Enter 33 for Telephone Line 1
1=SIA, 2=Contact ID
Format is: _
Press <#> when done
or <*> to cancel.
13. Select the Fire Alarm Protocol by entering 54 (Item number), the following screen will appear,
1=FA type, 2=FX type
UDACT type: _
Press <#> when done
or <*> to cancel.
Select FA by typing 1, if the Fire Alarm used is an FA-1000. Select FX by typing 2, if the Fire Alarm used is an FX-2000.
14. Enter 11 to initiate the test report, the screen will go through the following sequences:
Digital Communicator
[Testing Line DC]
Date
Time
Press any key to start login procedure (scrolls horizontally)
If it stays in the testing line DC screen, then the polarity of the phone line may be reversed, the phone line is not
operating properly or the UDACT-100A is not the first piece of equipment on the telephone line. If the telephone line is
good, the next screen should be,
Digital Communicator
[Wait for DIALtone]
Date
Time
Note: It will wait for dial tone if selected as such, see Item 63 in System Configuration & Operation section.
If the screen stays in the Wait for Dialtone mode, then there is a telephone line failure, otherwise the next screen is,
Enter 43 for Telephone Line 2
1=SIA, 2=Contact ID
Format is: _
Press <#> when done
or <*> to cancel.