24 hours exceeds the threshold in the UDACT-100A, a Communication Trouble with ID#485 will be reported during the 24-hour periodic test. The UDACT-100A is capable of reporting multiple events to a single Account number, within a single call session. Up to 3 retries, for a single message not yet reported, will be made within a single call- attempt.
FCC. Contact your telephone company if you have any questions about your phone line. In the event repairs are ever needed on the Communicator, they should be performed by Mircom Technologies Ltd. or an authorized representative of Mircom Technologies Ltd.
MECHANICAL INSTALLATION AND DIMENSIONS The UDACT-100A board is a single PCB assembly 7-11/16” by 4-7/16”. It’s mechanical installation is determined by the Fire Alarm Control Panel (FACP) they are being installed in, and is described in the appropriate FACP Installation Manual.
FIELD WIRING UDACT-100A MAIN BOARD TERMINAL CONNECTIONS: Wire the two telephone lines devices to terminals as shown. Line 1 Input (Tip/Ring): To the first Telephone Line via the required RJ31X Connector. Line 1 Output (Tip/Ring): To an optional Premise Telephone on the first Telephone Line via the required RJ31X Connector.
POWER UP PROCEDURES 1. Unplug Fire Alarm Panel. 2. Connect cable from P2 on the UDACT-100A board to the Fire Alarm Panel. Check the Fire Alarm manual for the UDACT-100A cable location. 3. Hook up the CFG-100 Configuration Tool to P4 on the UDACT-100A.
Page 8
If it stays in the testing line DC screen, then the polarity of the phone line may be reversed, the phone line is not operating properly or the UDACT-100A is not the first piece of equipment on the telephone line. If the telephone line is...
Page 9
The above sequence should occur only once for a successful report. If the “Reporting Event” fails the UDACT-100A will try 3 more times within the same phone call. If this fails the UDACT-100A will hang up and redial and try again.
SYSTEM CONFIGURATION & OPERATION The Mircom Digital Communicator is configured by connecting the CFG-100 Configuration Tool to P4 of the UDACT-100A Main Board. Once connected, if no text appears immediately on the LCD screen, hit any key on the numeric keypad.
Page 11
ITEM Access Menu Category Menu Label Description Number Level Account (#1) Account ID #1 Assign 4-6 numeric Account ID to be identified with Account #1 monitoring station receiver. Account (#1) Dial-Prefix #1 (OPTIONAL) Set up-to-8-digits to be first dialed by UDACT when attempting to call Account #1 monitoring station receiver.
The UDACT-100A works by eavesdropping on status communication messages within either the FA-1000 or the FX-2000 fire alarm system. As a consequence of this method of operation, the UDACT-100A reports events slightly differently depending upon whether it is eavesdropping on an FA-1000 or an FX-2000. Use command Item Number 54 to select between FA-1000 reporting and FX-2000 reporting.
Page 13
4 will be reported at the central station as an alarm on zone 5. Additionally, for the same FX-2000 fire panel, if there is a trouble on internal output circuit 6, the UDACT-100A will report a trouble on output zone 7 at the central station.
Page 14
ADEMCO CONTACT-ID UDACT-100A Internal Events : Event Description Event Family Qualifier Code Group # Contact # Phone Line #1 trouble detected Trouble New event 1 351 Phone Line #2 trouble detected Trouble New event 1 352 Phone Line #1 trouble restored...
* SIA protocol does not define indicating zone troubles, but lists it as Untyped Zone Trouble/Restore. COMPATIBLE FIRE ALARM CONTROL PANELS Mircom UDACT-100A: Compatible with Mircom FA-1000 Series and FX-2000 Series Fire Alarm Control Panels. COMPATIBLE RECEIVERS The Mircom UDACT-100A is compatible with the following Digital Alarm Communicator Receivers (DACR) ...
UDACT-100A Digital Communicator: M Connects to two Telephone Lines and performs DC Supervision. M Connects to a Mircom FACP via a ribbon cable. This connection provides DC power, RS-485 Data Link, and all other signalling between the Communicator and the FACP.
MIRCOM Technologies Ltd., manufactured equipment is guaranteed to be free of defects in material and workmanship for a period of one (1) year from the date of original shipment. MIRCOM will repair or replace, at its option, any equipment which it determines to contain defective material or workmanship.
UDACT-100A INFORMATION FORM Account #1 Identification (max. 6 digits): _ _ _ _ _ _ Account #1 Telephone number (including area code): __________________________ Telephone number of receiving station (including area code) : ____________________ 9 Contact ID Reporting Format: 9 SIA _________________________________________________________________________________________ Account #2 Identification (max.