R 11/92
Contents of Status Register 3
7
6
5
4
3
2
s
s
Status after RESET
7
6
5
4
3
2
x
x
x @ ~ o @ o
Wire break message is not queued: O
@ C o u n t e r 2submoduleis p r e s e n t : 1
Counter 2 submodule is not present: O
Illegal operating
Monitors the parameterization. The bit is automatically set to O when the
mode (IOM)
set (+ section 6.4).
Counter 2 sub–
This bit indicates whether the plug– in submodule is installed.
module inserted
Module
After the 1P 281 has been parameterized, the S5 can use control register3
(set bit 2) to report that the module is parameterized. Assoonasthe bit has
been set (during startup) in the control register, it can be read back via the
status register for monitoring purposes.
This status bit remains set as long as operation of the module is "normal". It
is deleted when a supply voltage failure occurs or the S5 initiates a RESET
(i.e., the parameterization is lost).
As soon as a wire break occurs on the RS 422 encoder interface
Wire break,
counters 1/2
break recognition is active. Reading the status register causes the bitto be
reset if no more errors are queued.
Bit 4/5
AG 1992, Order No: 6ES5 998-0KP21
1
0
s = Static
d
d = Dynamic
I
O: Operating mode setting is legal.
1: Operating mode setting is incorrect.
Counter 2 submodule inserted
O: No
1: Yes
Module psrsmeterized
O: No
1: Yes
Wire bresk, counter 1
O:
No
1: Yes
O: No
1: Yes
Disregard
1
0
Commissioning the Counter Module
Status bit is not reset.
5 – 7