Parameter Name - Danfoss EKD 316C Colibri Installation Manual

Electronic superheat controller

Advertisement

For detail parameter list and explanation, please check the EKD 316C Manual.
Application specific setup

Parameter Name

o10
Ai type
o18
Manual control
o30
Refrigerant
o61
App. mode
o20
Min. trans. press.
021
Max. trans. press
r12
Main switch
Valve configuration
Parameter Name
n03
Valve type
n37
Max. steps x 10
n38
Max. step / second (PPS) 3033
n39
Start backlash (% of FS)
n40
Backlash (steps)
n56
Motor current (mA)
Note: Please refer to Danfoss EKD 316 manual for details.
Parameter setup
A
.
Setting controller in Superheat control mode.
Make sure that r12 = 0 (OFF) and change the settings
The setting will depends on the system requirement.
Select Refrigerant
o30 = 1-42 (default non selected)
Select valve type
n03 = 0 - 9 (default is "non" i.e non valve selected).
On using EKA 164A display, check the valve
overview chart.
Define pressure sensor range in gauge bar
o20 = Min. Transducer pressure
o21 = Max. Transducer pressure
Set the application mode
For MSS control n21 = 1 (default)
For Load define control n21 = 2
Define min/max superheat
n10 = min. superheat reference
n09 = max. superheat reference
For fixed superheat define n09 = n10
Define MOP (optional)
n11 = maximum operating pressure
(default is 20 bar, max. 200 = MOP off)
Set force opening of the valve ( optional)
Start OD% (n17)
StartUp time (n15)
To start the supeheat control
Set r12= ON
DKRCC.PI.RR0.A3.02
A. Superheat control
Use as controller (SH).
PNU
Value
2027
No signal
2075
No override
2551
See EKD instruction for
refrigerant setting.
2077
2 = Superheat
2034
Min. value on transmitter
2033
Max. value on transmitter
117
On
PNU
Description
3002
Define the proper valve type, check Valve overview for detail
3032
Total number of full steps. on using EKA display, 800 step is
display as 80.
define the require/recommended steps per sec.
3034
(extra closing steps at 0 % opening (in % of n37))
3035
Compensation for spindle play
3051
Define the require current in mA RMS.
B
.
Setting controller in valve driver mode
using analog signal
Make sure that r12 = 0 (OFF) and change the
settings so they fit to their application:
Select Appication mode
o61 = 1 (remote/AI control)
Select Analog signal type
o10 = 2 (4-20mA)
(for other analog signal check the parameter list)
Select valve type
n03 = 17 (valve type, ETS C = 17)
for other valve types refer to valve overview table.
To start the controller in Valve driver mode
Set r12 = ON
B. Valve driver
Using analog signal.
Value
0 - 20 mA / 4 - 20 mA / 0 - 10 V / 1 - 5 V
No override
See EKD instruction for
refrigerant setting.
1= Valve driver using analog signal
-
-
On
Danfoss
84B3193.10
© Danfoss A/S (AC-MCI / sw), 2016-12