Stepper Motor Output
• All Valves are driven in a bipolar mode with a 24V supply that is chopped to control the current (Current driver).
• The stepper motor is connected to terminals 5 to 8 (see terminal assignment) with M12 motor cable.
• To configure stepper motor valves other than Danfoss stepper motor valve, it is necessary to set the right
valve parameters as described on section Valve configuration. The default valve setting in EKD 316C is
16 (i.e. 'non')
• It is neccesary to define correct valve in 'Valve type' i,e parameter n03. The overview of the valve types has
been defined in section "valve overview".
Valve overview
n03
EKA 164A
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
DKRCC.PI.RR0.A3.02
Danfoss valve type
ETS 12.5, ETS 25, KVS 15
ETS 50, CCM 10, CCM 20, CCM30
ETS 100, CCM 40
ETS 250, KVS 42
ETS 400
User defined
UKV/SKV/VKV/PKV
ETS 6
CCMT 2, CCMT 4, CCMT 8
CCMT 16
CCMT 24
CCMT 30
CCMT 42
CTR
CCMT 0
CCMT 1
No valve selected
ETS 12C, ETS 24C, ETS 25C, ETS 50C, ETS 100C, KVS 2C, KVS 3C, KVS 5C
n37
262
262
353
381
381
-
24
24
110
80
140
230
220
660
24
24
10
60
© Danfoss A/S (AC-MCI / sw), 2016-12
n38
300
300
300
300
300
-
16
16
220
200
200
200
200
75
16
16
160
160