Altronix OLS120D2X dual output power supply/charger converts a 115VAC, 50/60Hz or 230VAC, 50/60Hz
input to a 12VDC/24VDC output and a 12VDC fixed output (see specifications). This unit has a wide range of
applications for access control and security system accessories that require additional power.
Input:
• Universal input 115VAC, 50/60Hz, 0.95A or
230VAC, 50/60Hz, 0.6A.
• Input fuse rated @ 5A/250V.
Output:
• DC1: 12VDC or 24VDC @ 3A.
DC2: 12VDC @ 1A.
Note: If DC2 is not used, DC1 rating is
12VDC or 24VDC rated @ 4A max.
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
Wiring methods should be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI and with
all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes
in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place
the enclosure's upper keyholes over the two upper screws; level and secure. Mark the position of the lower
two holes. Remove the enclosure. Drill the lower holes and install three fasteners. Place the enclosure's
CAUTION: De-energize unit prior to servicing.
upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all
screws (Enclosure Dimensions, pg. 4). Secure enclosure to earth ground.
2. Slide [Power ON/OFF] switch t o the OFF position (Fig. 1, pg. 3).
3. Set the DC1 output voltage via DIP switch: OFF for 24VDC operation or ON for 12VDC operation
(Fig. 1, pg. 3). DC2 output voltage is fixed at 12VDC operation.
Keep power-limited wiring separate from non power-limited wiring (115VAC/230VAC, 50/60Hz
Input, Battery Wires). Minimum 0.25" spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or
servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to
Ground
qualified service personnel.
Wire
4. Connect AC circuit (115VAC or 230VAC, 50Hz/60Hz) as follows: Green branch wire connects to earth
Strap
(safety) ground
(from
Use 18 AWG or larger for all power connections (Battery, DC output).
Enclosure
Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).
to Door)
5. Slide [Power ON/OFF] switch t o the ON position (Fig. 1, pg. 3).
6.
Measure output voltage across both output terminals marked [– DC1 +], [– DC2 +] before connecting
115/230VAC
devices. This helps avoiding potential damage.
power mains
7.
Slide [Power ON/OFF] switch t o the OFF position (Fig. 1, pg. 3).
8. Connect 12VDC or 24VDC (depending on DIP switch setting) device to be powered to the terminals
marked [– DC1 +]. Connect 12VDC device to be powered to the terminals marked [– DC2 +] (Fig. 1, pg. 3).
9. When use of stand-by batteries is desired, they must be lead acid or gel type.
Circuit
Connect battery/batteries to the terminals marked [– BAT + ] (Fig. 1, pg. 2).
12VDC operation only: Use one (1) 12VDC battery for 12VDC backup.
24VDC and 12VDC simultaneous operation: Use two (2) 12VDC batteries connected in series for
24VDC backup.
10. When batteries are not used, a loss of AC will result in the loss of output voltage.
11. Connect appropriate signaling notification devices to AC Fail & Low battery supervisory
relay outputs marked [NC, C, NO].
12. Slide [Power ON/OFF] switch to the ON position (Fig. 1, pg. 3).
OLS120D2X
Dual Output Offline Power Supply/Charger
Installation Instructions:
ON
Lug
. Line and Neutral to the connector on power supply board marked [L, N] respectively.
LOW BAT
Overview:
Features:
Battery Backup (cont'd):
• Automatic switch over to stand-by battery
when AC fails.
• Maximum charge current 0.7A.
Supervision:
• AC fail supervision (form "C" contacts).
• Low battery supervision (form "C" contacts).
Visual Indicators:
• AC input and DC output LED indicators.
Features:
• Power ON/OFF switch (interrupts mains).
• Includes battery leads.
Enclosure Dimensions (H x W x D approx.):
13.5" x 13" x 3.25" (342.9mm x 330.2mm x 82.6mm)
• Accommodates two (2) 12VDC/7AH batteries.
OFF
--- DC2 +
Switch disables power
ON
OFF
mains line voltage input.
If stand-by battery (batteries)
connected, the DC output rem
LED Diagnostics
Red Green Power Supply Status
(DC) (AC)
ON
ON
Normal operating condition
ON
OFF
Loss of AC. Stand-by batte
(batteries) supplying power
OFF ON
No DC output.
OFF OFF
Loss of AC. Discharged or
no stand-by battery (batteri
No DC output.
ON
DC1 Switch Setting
24VDC output - OFF