OPERATION

CONNECTING TO LARGE LPG/PROPANE TANK

BEFORE CONNECTING PROPANE TANK TO
THE GENERATOR PLEASE REVIEW FUEL
SAFETY SECTION ON PAGE 9
You can hook up you Duel Fuel Generator to a large home
LP tank. It is required that you consult a plumber to properly
connect your generator to the tank.
To properly connect with a large propane tank you must first
check and confirm the LP fuel pressure at the outlet of the
LP tank. The LP fuel pressure should be 14-10" of water
column, which is the standard fuel pressure for residential
gas fired appliances.
If the LP fuel pressure is within the 14-10" water column
range, the primary fuel regulator should be removed from
the fuel line components. Then plumb directly from the LP
tank to the secondary regulator assembled to the generator.
You must consult a certified plumber to connect
to large LP tank safely.

BEFORE STARTING THE GENERATOR

BEFORE STARTING THE GENERATOR,
REVIEW SAFETY SECTION STARTING ON
PAGE 5.
Before attempting to start the generator,
verify the following:
• The engine is filled with engine oil.
• The generator is situated in a proper location.
• The generator is on a dry surface.
• All loads are disconnected from the generator.
• The generator is properly grounded.
• Propane connection is secure with no leaks or damage.
Never use the generator in a location that is wet or
damp. Never expose the generator to rain, snow,
water spray or standing water while in use. Protect
the generator from all hazardous weather conditions.
Moisture or ice can cause a short circuit or other
malfunction in the electrical circuit.
Never operate the generator in an enclosed area.
Engine exhaust contains carbon monoxide. Only
operate the generator outside and away from
windows, doors and vents.
WARNING
DANGER
NOTICE
The engine is equipped with a low oil shutdown
switch. If the oil level becomes low, the engine may
shut down and not start until the oil is filled to the
proper level. Poor oil quality may interfere with the
operation of the low oil shutdown switch.
The owner of the generator is responsible to ensure
the proper oil level is maintained during the operation
of the generator. Failure to maintain the proper oil
level can result in engine damage.
NOTICE
When operating on LPG it is common for frost to form
on the tank and regulators. This is not an indication
of a problem. The amount of frost that forms can
be affected by the size of the container, the amount
of fuel being used, the humidity of the air and other
operating conditions. In standard use this frost may
reduce flow of gas and lower performance. If frost
becomes an issue try exchanging fuel tanks to allow
the first tank to warm up. You can also temporarily
warm the tank up by pouring warm water over the top
of the propane tank.
SWITCHING FUEL SOURCES
If you are switching fuel sources make sure to shut the
generator down first and follow instructions on starting
with your desired fuel source.
NOTICE
If you do not plan on operating the unit on propane
do not leave the propane tank valve open.
When starting on propane the engine may run rough
for a few seconds while it purges gasoline in the
carburetor.
Westinghouse Outdoor Power Equipment | 19