Manual Configuration Of The Additional Components - Siemens SINAMICS S120 Faq

About drive technology
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

SINAMICS S120 at Technology CPU Entry ID: 21767896
No.
10.
Components which do not feature a DRIVE-CLiQ interface are not detected
during the automatic configuration and have to be manually configured.
Using the automatic configuration of the DRIVE-CLiQ components, also
Note
hardware components with DRIVE-CLiQ interface can be configured
which are not included in the lists for the manual configuration and for
which manual configuration is very difficult.
6.2

Manual configuration of the additional components

The second servo motor of the SINAMICS S120 training case is not
equipped with a DRIVE-CLiQ interface. This motor is connected to the
SINAMICS S120 drive system via the SMC20 sensor module cabinet.
In S7T Config, manually configure these not automatically configured
components, in this case the drive SERVO_03, as follows:
Table 6-2 Manual configuration of the drive SERVO_03
No.
1.
V1.0
Instruction
Instruction
Edition 10/28/05
Commissioning SINAMICS S120
Commissioning SINAMICS S120
Note
Save and compile the new
configuration by clicking the
corresponding menu item.
Note
In the SIMATIC Manager, select
SINAMICS_S120 and double-click
this component in the right
window.
This starts S7T Config for
SINAMICS S120.
For manual configuration, leave
S7T Config in offline mode!
37/58