Advertisement

A.3.2

Instance DB for FB 59 "TCONT_S"

Parameter:
Addr Parameter
Decl.
0.0
CYCLE
INPUT
4.0
SP_INT
INPUT
8.0
PV_IN
INPUT
12.0
PV_PER
INPUT
14.0
DISV
INPUT
18.0
LMNR_HS
INPUT
PID Temperature Control
A5E00125039-02
Data
Range of
Type
Values
≥ 0.001
REAL
REAL
Dependent
on the
sensors
used
REAL
Dependent
on the
sensors
used
INT
REAL
BOOL
Initial
Description
Value
SAMPLE TIME OF STEP
0.1 s
CONTROLLER [s]
At this input, you enter the sampling
time for the controller.
0.0
INTERNAL SETPOINT
The "Internal Setpoint" input is used
to specify a setpoint.
PROCESS VARIABLE IN
0.0
An initialization value can be set at
the "Process Variable In" input or
an external process variable in
floating-point format can be
connected.
0
PROCESS VARIABLE
PERIPHERY
The process variable in the
peripheral I/O format is connected
to the controller at the "Process
Variable Peripheral" input.
0.0
DISTURBANCE VARIABLE
For feedforward control, the
disturbance variable is connected to
the "Disturbance Variable" input.
FALSE
HIGH LIMIT SIGNAL OF
REPEATED MANIPULATED
VALUE
The signal "valve at upper limit
stop" is connected to the "Upper
limit stop signal of the position
feedback signal".
LMNR_HS=TRUE: The valve is
at the upper limit stop.
Appendix
A-13