Siemens SIMATIC Manual page 86

Pid temperature control
Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Appendix
Addr
Parameter
116.0
PI_CON
GAIN
+0.0
TI
+4.0
124.0
PID_CON
GAIN
+0.0
TI
+4.0
TD
+8.0
136.0
PAR_SAVE OUTPUT STRUCT
PFAC_SP
+0.0
GAIN
+4.0
TI
+8.0
TD
+12.0
D_F
+16.0
CON_
+20.0
ZONE
CONZ_ON
+24.0
162.0
PFAC_SP
166.0
GAIN
A-8
Decl.
Data
Range of
Type
Values
OUTPUT STRUCT
OUTPUT REAL
%/phys.unit
≥ 0.0 s
OUTPUT REAL
OUTPUT STRUCT
OUTPUT REAL
≥ 0.0 s
OUTPUT REAL
≥ 0.0 s
OUTPUT REAL
INPUT/
REAL
0.0 to 1.0
OUTPUT
OUTPUT REAL
%/phys.unit
≥ 0.0 s
INPUT/
REAL
OUTPUT
≥ 0.0 s
INPUT/
REAL
OUTPUT
OUTPUT REAL
5.0 to 10.0
≥ 0.0
OUTPUT REAL
OUTPUT BOOL
INPUT/
REAL
0.0 to 1.0
OUTPUT
INPUT/
REAL
%/phys. unit 2.0
OUTPUT
Initial
Description
Value
PI CONTROLLER PARAMETERS
PI PROPORTIONAL GAIN
0.0
PI RESET TIME [s]
0.0 s
PID CONTROLLER
PARAMETERS
PID PROPORTIONAL GAIN
0.0
0.0 s
PID RESET TIME [s]
PID DERIVATIVE TIME [s]
0.0 s
SAVED CONTROLLER
PARAMETERS
The PID parameters are saved in
this structure.
PROPORTIONAL FACTOR FOR
1.0
SETPOINT CHANGES
PROPORTIONAL GAIN
0.0
40.0 s
RESET TIME [s]
DERIVATIVE TIME [s]
10.0 s
5.0
DERIVATIVE FACTOR
CONTROL ZONE ON
100.0
FALSE
CONTROL ZONE
1.0
PROPORTIONAL FACTOR FOR
SETPOINT CHANGES
PFAC_SP specifies the effective P
action when there is a setpoint
change. This is set between 0 and
1.
1: P action has full effect if the
setpoint changes.
0: P action has no effect if the
setpoint changes.
PROPORTIONAL GAIN
The "proportional gain" input
specifies the controller gain. The
direction of control can be reversed
by giving GAIN a negative sign.
PID Temperature Control
A5E00125039-02