Technical Data; General Unit Data; Environmental Conditions - Siemens LFL1.133 Manual

Burner controls
Table of Contents

Advertisement

Technical data

General unit data

LFL1...
Environmental
conditions
10/25
Building Technologies Division
Mains voltage
Mains frequency
Unit fuse (built-in)
Primary fuse (external)
Weight
Power consumption
Mounting position
Degree of protection
Safety class
Perm. input current at terminal 1
Perm. load on control terminals 3, 6, 7,
9...11, 15...20
Required switching capacity of switching
devices
Between terminals 4 and 5
-
Between terminals 4 and 12
-
Between terminals 4 and 14
-
Permissible length of the standard detector
cable (laid separately)
Capacity
Output on startup (without fan
-
assistance)
Nominal output
-
Storage
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Transport
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Operation
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Installation altitude
Warning!
Condensation, formation of ice and ingress of water are not permitted!
If not observed, there is a risk of impairment of safety functions and of
electric shock hazard.
AC 230 V –15 / +10 %
AC 100 V –15%...AC 110 V +10%
50...60 Hz ±6 %
T6.3H250V to DIN EN 60 127
max. 10 A (slow)
approx. 1,000 g
approx. AC 3.5 VA
optional
IP 40, when built in, with the exception of
the connection area (terminal base)
II
max. 5 A continuously (peaks 20 A / 20 ms)
max. 4 A continuously (peaks 20 A / 20 ms)
1 A, AC 250 V
1 A, AC 250 V
min. 1 A, AC 250 V
depending on the load on terminals 16...19
See Technical Data, chapter Flame
supervision
Optional (with ignition <120 kW)
Optional
DIN EN 60721-3-1
class 1K3
class 1M2
-20...+60 °C
< 95 % r.h.
DIN EN 60721-3-2
class 2K3
class 2M2
-20...+60 °C
< 95 % r.h.
DIN EN 60 721-3-3
class 3K3
class 3M3
-20...+60 °C
< 95 % r.h.
Max. 2,000 m above sea level
CC1N7451en
20.11.2017