Legend - Siemens LFL1.133 Manual

Burner controls
Table of Contents

Advertisement

Legend

a
Changeover end switch for air damper's OPEN position
AL
Remote lockout warning device (alarm)
AR
Load relay with contacts «ar...»
AS
Unit fuse
BR
Lockout relay with contacts «br...»
BV...
Fuel valve
bv...
Control contact for the CLOSED position of gas valves
d1 / d2
Contactor or relay
EK...
Lockout reset button
FR
Flame relay with contacts «fr...»
FS
Flame signal
GP
Gas pressure switch
H
Main isolator
ION
Ionization probe
L1
Fault signal lamp
L3
Operational readiness indication
LK
Air damper
LP
Air pressure switch
LR
Load controller
M1 / M2 Fan or burner motor
m
Changeover auxiliary switch for the air damper's MIN position
NTC
NTC resistor
QRA...
UV detector
R
Control thermostat or pressurestat
RV
Modulating fuel valve
SA
Air damper actuator
SB
Safety limiter
Si
External fuse
SM
Synchronous motor of sequence switch
V
Flame signal amplifier
v
In the actuator: Changeover auxiliary switch for the position-dependent release of fuel
W
Limit thermostat or pressure switch
Z
Ignition transformer
z
In the actuator: End switch for the air damper's CLOSED position
ZBV
Pilot gas valve
(1)
Input for increasing the operating voltage for the QRA2 / QRA4 / QRA10 (detector test)
(2)
Input for forced energizing of the flame relay during the functional test of the flame supervision circuit
(contact XIV ) and during safety time «TSA» (contact IV )
Valid for direct spark flame burners

Valid for interrupted pilot burners with a pilot burner, which is switched off following the ignition of the main
burner
A
Start command given by the temperature controller
A-B
Startup program
B
Operating position of the burner
B-C
Burner operation
C
Controlled shutdown via control thermostat or pressurestat (R)
C-D
Sequence switch runs to the end position following controlled shutdown via control thermostat or
pressurestat (R)
End position of the burner control  corresponds to the start position
D-A
Control signals of the burner control
Permissible input signals
Required input signals:
If these signals are not present at the points in time marked by symbols or during the hatched periods of
time, the burner control interrupts the startup sequence or initiates lockout
Building Technologies Division
23/25
CC1N7451en
20.11.2017