TEMPERATURE ADJUSTMENT

Rotate the adjustment knob counter clockwise for a
warmer setpoint or clockwise for a colder setpoint.
• While the temperature is being adjusted, the optional
display shows the setpoint (cut out value). A few
seconds after the temperature is set, the display
reverts to showing the sensed temperature in the
merchandiser.
ALARMS AND CODES
FLASHING TEMPERATURE OR SENSOR ALARM LED,
E1 OR E2
If the Temperature or Sensor Alarm LED (red) on the
controller and display is fl ashing, a temperature sensor
has failed. The display shows E1 if the case sensor has
failed or E2 if the evaporator sensor has failed.
If the merchandiser sensor fails, refrigeration will run
continuously. Turn off, or repeat a duty cycle of a few
minutes on and a few minutes off.
DEFROST TERMINATION SWITCH
Merchandisers may use a defrost termination switch,
instead of an evaporator sensor to terminate a defrost
cycle. The defrost termination switch is temperature
Safe-Net III Operation (Cont'd)
activated and senses the completion of defrost.
Compressor
Off Time If
Sensor Failed
Compressor
Status
Off
Off
MANUAL DEFROST
Warm
Cold
Note location of
1.
knob setting
Warm
Cold
Rotate knob fully
2.
counterclockwise
until it stops (full
warm- "OFF" position)
Warm
Cold
3.
After 10 seconds, but
before 20 seconds,
rotate knob fully
clockwise until it
stops (full cold position)
IMPORTANT: Return the control knob to its original
setting (Step 1) once the manual defrost has been
initiated.
19
Compressor
On Time If
Sensor Failed
On
Off
On
Note:
This procedure initiates
a manual or forced
defrost
Time