Md-P1 Point Map By Application Number With Point Map Comparison - Siemens MD-P1 User Manual

Power meters
Table of Contents

Advertisement

MD-P1 Point Map by Application Number with Point Map Comparison

Table 4: MD-P1 Point Map by Application Number with Point Map Comparison to DEM1000, DEM2000
P1
Point
Type
P1 Name
Point
Type
No.
1
LAI
3
ADDRESS
2
LAO
4
APPLICATION
3
LAI
3
FREQUENCY
4
LAI
3
KW DEM MAX
5
not used
6
LAI
3
KW DEM MIN
7
LAI
3
KW
8
LAI
3
CONSUMPTN LO
9
LAI
3
CONSUMPTN HI
10
LAI
3
DEMAND
Units
Default
Detail
Value
99
MD-P1 rotary hex switch (MSB and
LSB) on front of meter
Application
P1 Application Number based on
Number
selected CT Current Range
(can only change via WCIS tool)
Hz
0
Measured Line Frequency
kW
0
System Maximum Power Demand
or Peak Demand
- returns max demand value read
since startup or reset of demand
register
not used
kW
0
System Minimum PowerDemand
- returns min demand value read
since startup or reset of demand
register
kW
0
System Total True Power =
ABS(kW L1) + ABS(kW L2) +
ABS(kW L3)
System Total Net True Energy LSW
kWh
0
=ABS(kWh L1) + ABS(kWh L2) +
ABS(kWh L3)
kWh
0
System Total Net True Energy
MSW
=ABS(kWh L1) + ABS(kWh L2) +
ABS(kWh L3)
System Average Power Demand
kW
0
Slope
Intercept
MD-P1
MD-P1
for P1
for P1
Series**
Series*
Apps
Apps
Apps
*
2771-
App
2777
2779
1
0
1
0
0.1
0
0.1
0
0.1
0
0.1
0
1.0
0
1.0
0
0.1
0
DEM1000*
DEM2000*
Apps 710-
Apps 717-
716
723

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Md-p1d

Table of Contents