Siemens LOK16 Series Manual page 9

Burner controls
Hide thumbs Also See for LOK16 Series:

Advertisement

Technical data
General unit data
LOK16.../LGK16...
Environmental
conditions
Building Technologies Division
Infrastructure & Cities Sector
Mains voltage
Mains frequency
Unit fuse
Primary fuse (external)
Weight
Power consumption
Perm. mounting position
Degree of protection
Safety class
Perm. input current at terminal 1
Perm. current load of control terminals
Required switching capacity of switching
devices
Between terminals 4 and 5, 4 and 12
-
Between terminals 4 and 14
-
Storage
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Transport
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Operation
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Caution!
Condensation, formation of ice and ingress of water are not permitted!
AC 220 V -15%...AC 240 V +10%
AC 100 V -15%...AC 110 V +10%
50...60 Hz ±6%
T6,3H250V to DIN EN 60 127
Max. 16 A (slow)
Approx. 1000 g
Approx. 3.5 VA
Optional
IP40, (to be ensured through mounting)
with the exception of the connection area
(terminal base)
II
Max. 5 A to VDE 0660 AC3
Max. 4 A to VDE 0660 AC3
1 A, AC 250 V
depending on loading of terminals 15, 16,
18, 19 (LGK16...: 16...19), min. 1 A,
AC 250 V
DIN EN 60721-3-1
Class 1K3
Class 1M2
-20...+60 °C
<95% r.h.
DIN EN 60721-3-2
Class 2K3
Class 2M2
-20...+60 °C
<95% r.h.
DIN EN 60721-3-3
Class 3K3
Class 3M3
-20...+60 °C
<95% r.h.
9/24
CC1N7785en
06.03.2012