E5 K
Precautions
PRECAUTIONS WHEN WIRING
•
Use wire ducts to separate input leads and power lines in
order to protect the Controller and its lines from external
noise.
•
Solderless terminals are recommended when wiring the Con-
troller.
Power Blocks
The E5AK/E5EK has independent power supplies for each of the terminal blocks shown below.
E5AK
10
30
20
31 32
9
29
19
8
28
18
7
27
17
6
26
16
*
5
25
15
4
24
14
3
23
13
2
22
12
33
1
21
11
* Uses same internal power supply
Note: Terminals 21 and 22 of the E5EK belong to the B block when a transfer output is set to option 1 and to the C block for other
Option Boards.
OPERATING ENVIRONMENT
•
Keep within the rated ambient operating temperature, ambi-
ent operating humidity, and storage temperature ranges.
•
Use the Unit according to the vibration resistance, shock
resistance, and enclosure ratings.
•
Do not use the Unit in places with corrosive gas or excessive
dust.
•
Do not use the Unit near machines generating high-frequen-
cy noise.
CORRECT USE
Mounting
•
The dimensions of the Digital Controller conform to DIN
43700.
•
Recommended panel thickness is 1 to 8 mm.
•
Mount the Unit horizontally.
E5EK
*
10
9
8
7
6
5
4
3
2
1
•
Tighten the terminal screws using a torque no greater than
0.78 N
m, or 8 kgf
terminal screws too tightly.
*
*
20
21 22
19
18
17
16
15
14
13
12
23
11
Connection
•
To reduce inductive noise influence, the lead wires connect-
ing the input type to the Digital Controller must be separated
from the power lines and load lines.
•
Use the specified compensating conductors for thermocou-
ples. Use lead wires having a small resistance for platinum
resistance thermometers.
Connection Example
•
Wire the terminals of the Unit using solderless terminals.
•
The tightening torque applied to the terminal screws of the
Unit must be approximately 0.78 N
Use the following type of solderless terminals for M3.5 screws.
7.2 mm max.
7.2 mm max.
cm max. Take care not to tighten the
E5CK
*
5
11 12
10
4
9
3
8
*
2
7
1
13 14 6
m or 8 kgf
cm.
E5 K