E5 K
Option Mode - - ONLY Visible if an Option Board is Installed

E5
K
  

  

E5AK and E5EK only
   
   
   

COMMUNICATIONS FUNCTION
  

 
  


!
  

(continued on next page)
Multi-SP Function
Specifies the number of set points that will be used. Must be set to one to use SP Ramp feature.
Available for the event input function. Default = 0
Event Input Assignment 1
Available for the event input function. If multi-SP is set to 0, this parameter assigns event input
function as: Run/Stop, Auto/Manual, or Protect Function. Default = Stop.
Event Input Assignment 2
Available for the event input function.
Event Input Assignment 3
Available for the event input function.
Event Input Assignment 4
Available for the event input function.
Communication Stop Bit
Displayed when the communications function is in use.
Range = 1 to 2
Default = 2
Communication Data Length
Displayed when the communications function is in use.
Range = 7 to 8
Default = 7
Communication Parity
Displayed when the communications function is in use.
Range = None, Even, Odd
Default = Even
Communication Baud Rate
Displayed when the communications function is in use.
Range = 1.2, 2.4, 4.8, 9.6, 19.2 k baud
Default = 9.6
Communication Unit No.
Displayed when the communications function is in use.
Range = 0 — 99
Default = 0
Communications selections are ONLY available if a commu-
nications board is installed.