11: Programmable outlets setting
LOAD
0-999:
limit in minutes from 0-999 for
BATTERY
9 9 9
1 1
programmable outlets which are
M
connected to non-critical devices on
battery mode (Default: 999).
12: Autonomy limitation setting
LOAD
Set up backup time on battery mode
for general outlets.
BATTERY
0-999:
d 1 5
1 2
minutes from 0-999 for general
M
outlets on battery mode.
DIS:
and the backup time will depend on
battery capacity. (Default)
Note: When setting as "0", the
backup time will be only 10 seconds.
13: Battery total AH setting
LOAD
Set up the battery total AH of the
BATTERY
7
UPS.
1 3
7-999:
capacity from 7-999 in AH.
26
you can set the backup time
setting the backup time in
Disable the autonomy limitation
setting the battery total
14: Maximum charger current setting
Set up the maximum charger current.
LOAD
When the UPS is equipped with
additional charger, the available
BATTERY
8
setting options are 2/3/4.
1 4
2/3/4:
setting the maximum charger
current in 2/3/4 Ampere.
When the UPS is long run model,
the available setting options are
1/2/4/6/8.
1/2/4/6/8:
charger current in 1/2/4/6/8
Ampere. (Default: 8A)
15: Charger Boost voltage setting
LOAD
Set up the charger boost voltage.
225-240:
BATTERY
V
2 3 6
1 5
voltage from 225 to 240(unit: 0.01V/
cell). (Default: 236)
16: Charger Float voltage setting
LOAD
Set up the charger float voltage.
BATTERY
22 8
V
220-233:
1 6
voltage from 220 to 233(unit: 0.01V/
cell). (Default: 228)
setting the maximum
setting the charger boost
setting the charger float