6 MAINTENANCE OF ELECTRICAL GENERATOR

You must make sure that the person who will perform this duty is qualified to do so
and utilizes the appropriate individual protection equipment.
6.1

PRIOR TO MAINTENANCE

You must first:
Switch Control Module to the STOP position.
Press the emergency stop button.
Open the battery isolator.
6.2

DURING MAINTENANCE

Preventive maintenance tasks are necessary to preserve the unit; doing so will result
in optimum performance. Be sure to verify the following items:
1)
While the Engine is cold, the oil level should be between the minimum and
maximum values. If it is below the minimum, add Engine oil.
Note: With the GPM-2 and InteliGen modules, after running 50 hours notice will be given to
change the oil. The recommended oil is 15W40.
2)
The radiator water level should be adequate.
3)
The fuel level in the tank should be sufficient for the service to be
performed. The generator control panel is equipped with a fuel gauge,
which will be functional whenever the electrical panel is receiving power.
4)
Always refuel in a well ventilated area with the engine stopped.
5)
Closely inspect the connections and the electrical circuit, for both the
mechanical and electrical sections.
6)
Check carefully for possible liquid leaks. If a leak is detected, find its
source and resolve the problem.
7)
The air inlet and outlet vents should be completely unobstructed to allow
for free circulation of cooling air.
8)
Check the battery's connection terminals and electrolyte level (if
necessary, add demineralized or distilled water). Acid should never be
USERS MANUAL
RENTAL SERIES ELECTRICAL GENERATOR
Page 50 of 62