Sai-Au M12 Sb 4Pt100 - Weidmuller SAI Active Universal Pro Series Manual

Table of Contents

Advertisement

5.13

SAI-AU M12 SB 4PT100

The SAI distributor Active Universal is equipped with
the functions of a decentralised I/O system. Each
distributor is equipped with module-specific actua-
tor/sensor functions and a sub-bus interface. The
modules combine the complete electronics in a wa-
ter- and dust-proof protected housing. This enables
their use in harsh environments.
The module SAI-AU M12 SB 4PT100 is designed to
connect four thermocouples with four M12 connec-
tors.
PT100
COM
IN
Figure 55
SAI-AU M12 SB 4PT100
5663600000/1.4/09.09
AI3
AI2
AI1
AI0
U
B
BUS
OUT
HINWEIS
After a change of the Subbus modules is
in many situations a new start of the ga-
teway necessary.
LEDs
UB
Supply voltage UB
Supplies the module and the
Plug-in stations 1 to 4
Com
Communication with the
gateway
AI0 to AI3
PT100 inputs
Connections
SUB IN
Sub-bus input
SUB OUT
Sub-bus output
1 to 4
4 inputs
Table 66
SAI-AU M12 SB 4PT100
Connection of supply voltage
The power supply is 24 V DC in accordance with
EN 61131-2; the permissible range is 18 to 30 V DC.
The distributor is designed to offer protection against
polarity reversal.
Module connection from SUB-IN
Contact system
M8 male connector, 4-pole
Coding
-
Pin assignment
Pin 1: + 24 Vdc
Pin 2: Data +
Pin 3: GND
Pin 4: Data -
Housing: Shield, connected
with the FE
Table 67
Contact assignment for the sub-bus
male connector
Connecting the SAI Distributor
85

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents