Commissioning the PROFIBUS-DP
6.9.2

Diagnostics with channel referred information

Parameter: „Extended Diagnostic" Enable
This diagnosis consists of four parts:
1. Six bytes of standard diagnostics
2. 35 bytes Device-related diagnosis
3. 2-3 bytes of identification-referred diagnosis (Number depends on number of attached Extension IO mod-
ules <= 7 = 2 bytes, >7 = 3 bytes)
4. n bytes channel-referred diagnosis (The channel-referred diagnosis is as largely as the number of arising
errors times three bytes)
Standard diagnostics
Byte 0, station status 1
Bit 0
station_non_exist
Bit 1
station_not_ready
Bit 2
cfg_fault
Bit 3
ext_diag
Bit 4
not_supported
Bit 5
invalid_slave_response
Bit 6
prm_fault
Bit 7
master_lock
Byte 1, station status 2
Bit 0
Prm_req
Bit 1
Stat_diag
Bit 2
"1"
Bit 3
WD_ON
Bit 4
freeze_mode
Bit 5
sync_mode
Bit 6
reserved
Bit 7
deactivated
128
1 = station can not be reached; always "0"
1 = station is not ready for data exchange
1 = configuration error with the master
1 = extended diagnostics data is available
1 = a requested function is not supported
1 = the slave response was not valid
1 = false or incomplete parameter data
1 = parameters are from another master set - access is locked
1 = parameter must be transmitted again
1 = diagnostic data is present
Slave always sets "1"
1 = The slave has activated the watchdog
1 = The slave has received the "freeze" control command
1 = The slave has received the "sync" control command
Slave always sets "0"
1 = set from master, slave is inactive, slave always sets "0"
5663600000/1.4/09.09