Identification-Specific Diagnostic Data - Weidmuller SAI Active Universal Pro Series Manual

Table of Contents

Advertisement

Commissioning the PROFIBUS-DP
6.9.4

Identification-specific diagnostic data

The identification-specific diagnostics indicates where (in which module) the error occurred.
Byte 41, identification-specific diagnostic header
Bit 0
The length in bytes of the identification-specific diagnostics
Bit 1
The length in bytes of the identification-specific diagnostics
Bit 2
The length in bytes of the identification-specific diagnostics
Bit 3
The length in bytes of the identification-specific diagnostics
Bit 4
The length in bytes of the identification-specific diagnostics
Bit 5
The length in bytes of the identification-specific diagnostics
Bit 6
The code for identification-specific diagnostics is always equal to 0.
Bit 7
The code for identification-specific diagnostics is always equal to 1.
Byte 42, details of the module where the errors occurred, modules 1-8 (including gateway I/O)
Bit 0
1 = error in gateway I/O
Bit 1
1 = error in extension I/O at position 1
Bit 2
1 = error in extension I/O at position 2
Bit 3
1 = error in extension I/O at position 3
Bit 4
1 = error in extension I/O at position 4
Bit 5
1 = error in extension I/O at position 5
Bit 6
1 = error in extension I/O at position 6
Bit 7
1 = error in extension I/O at position 7
Byte 43, details of the module where the errors occurred, modules 9-16
Bit 0
8 = error in extension I/O at position 8
Bit 1
9 = error in extension I/O at position 9
Bit 2
10 = error in extension I/O at position 10
Bit 3
11 = error in extension I/O at position 11
Bit 4
12 = error in extension I/O at position 12
Bit 5
13 = error in extension I/O at position 13
Bit 6
14 = error in extension I/O at position 14
Bit 7
15 = error in extension I/O at position 15
Table 92

Identification-specific diagnostic data

132
5663600000/1.4/09.09