Sai-Au M12 Sb 4Pt100; Sai-Au M12 Sb 4Thermo - Weidmuller SAI Active Universal Pro Series Manual

Table of Contents

Advertisement

Commissioning the PROFIBUS-DP
6.6.7

SAI-AU M12 SB 4PT100

Data
Describtion
input
4PT100
output
None
NOTE
It is possible to use the status data of the PT100 module as input data. Then the user must
chose the module named ""4PT100 M12 (input+status)".Then the input data are formed
of the two counters and the status data (as seen in the Chapter diagnostic data).
6.6.8

SAI-AU M12 SB 4THERMO

Data
Describtion
input
4THERMO
output
None
110
4 PT100 inputs
4 16bit wide words
temeratures:
16 bit two complement value :
1 Bit (digit) = 1/10 Kelvin
resistor values:
range up to 500 Ohm :
range up to 5k Ohm
4 THERMO inputs
4 16bit wide words
temeratures:
16 bit two complement value :
1 Bit (digit) = 1/10 Kelvin
voltages :
-250 to 250 mV :
-120 to 120 mV :
-60 to 60 mV :
-30 to 30 mV :
-15 to 15 mV :
range up to 5k Ohm
1 Bit (digit) = 0,01 Ohm
1 Bit (digit) = 0,1 Ohm
1 Bit (digit) = 8µV
1 Bit (digit) = 4µV
1 Bit (digit) = 2µV
1 Bit (digit) = 1µV
1 Bit (digit) = 0,5µV
1 Bit (digit) = 0,1 Ohm
5663600000/1.4/09.09