Electrical Data and Service Information
Table 2 and Table 3 show pump electrical service requirements for UMPs with end views A and B, respectively.
Table 4 shows pump electrical service requirements for EN 15268 UMPs with end view B.
Table 2. Electrical Service Information (For Umps Containing A Franklin Motor With End View A) - For STPs With UL,
cUL, 03ATEX0237289X, 04ATEX0330285X, 06ATEX6050X, ANZEX 04.3005X Or POCC 05.B02160 Markings
Required power supply rating for 60 Hz, 1 phase pumps is 208 - 230 Vac. For 50 Hz, 1 phase pumps, required rating is 220 - 240 Vac. For
3 phase pumps, required rating is 380 - 415 Vac.
UMP Model No.
HP
AGUMP33S1,
1/3
UMP33U1
AGUMP75S1,
3/4
UMP75U1
AGUMP150S1,
1-1/2
UMP150U1
X3AGUMP150S1,
1/1/2
X3UMP150U1
AGUMP200S1-3,
2
UMP200U1-3
AGUMP75S3-3,
3/4
UMP75U3-3
AGUMP150S3-3,
1-1/2
UMP150U3-3
X4AGUMP150S3,
1-1/2
X4UMP150U3
AGUMP200S3-4,
2
UMP200U3-4
AGUMP75S17-3,
3/4
UMP75U17-3
AGUMP150S17-3,
1-1/2
UMP150U17-3
X4AGUMP150S17,
1-1/2
X4UMP150U17
AGUMP200S17-4,
2
UMP200U17-4
Voltage
Fluctuation
Range
Hz
PH
Min.
Max.
Amps
60
1
200
250
60
1
200
250
60
1
200
250
60
1
200
250
60
1
200
250
50
1
200
250
50
1
200
250
50
1
200
250
50
1
200
250
50
3
342
457
50
3
342
457
50
3
342
457
50
3
342
457
Winding Resistance (Ohms)
Max.
Locked
Load
Rotor
Black-
Amps
Orange
4.0
13
7.7 - 9.4
6.5
25
2.9 - 3.6
10.5
37
2.0 - 2.5
10.5
37
2.0 - 2.5
11.4
46
1.4 - 1.7
5.8
17
3.6 - 4.5
10
28
2.5 - 3.1
10
28
2.5 - 3.1
11
37
1.9 - 2.4
2.2
8
25.8- 32.4
3.8
15
13.1 - 16.4
3.8
15
13.1 - 16.4
5.0
22
9.3 - 11.6
5
Red-
Capacitor Kit (µF)
Orange
Black-Red
or Heaters (KXX)
17.4 - 21.2
25 - 30.7
144-224-5 (17.5)
14.9 - 18.2
17.7 - 21.9
410164-001 (17.5)
11.6 - 14.2
13.5 - 16.8
410164-002 (25)
11.6 - 14.2
13.5 - 16.8
410164-002 (25)
2.5 - 3.2
3.8 - 5
410164-003 (40)
20.4 - 25
23.9 - 29.6
410164-001 (17.5)
11.5 - 14
13.9 - 17.2
410164-002 (25)
11.5 - 14
13.9 - 17.2
410164-002 (25)
3.1 - 3.9
5.0 - 6.3
410164-003 (40)
25.8- 32.4
25.8- 32.4
13.1 - 16.4
13.1 - 16.4
13.1 - 16.4
13.1 - 16.4
9.3 - 11.6
9.3 - 11.6
K26
K33
K33
K37