Temperature sensor, external flow line
If temperature sensor, external flow line (BT25) needs
to be used, connect it to terminal block X6:5 and X6:6
on the input card (AA3). Use a 2 core cable of at least
0.5 mm² cable area.
AA3-X6
F1145
F1145
Temperature sensor, external return line
If temperature sensor, external return line (BT71) needs
to be used, connect it to one of the AUX inputs on the
input board (AA3). Use a 2 core cable of at least 0.5 mm²
cable area.
9 10 11 12 13 14 15 16 17
F1145
F1145
Room sensor
F1145 is supplied with a room sensor enclosed (BT50).
The room sensor has up to three functions:
1. Show current room temperature in F1145's display.
2. Option of changing the room temperature in °C.
3. Makes it possible to change/stabilise the room
temperature.
Install the sensor in a neutral position where the set
temperature is required. A suitable location is on a free
inner wall in a hall approx. 1.5 m above the floor. It is
important that the sensor is not obstructed from meas-
uring the correct room temperature by being located,
for example, in a recess, between shelves, behind a cur-
tain, above or close to a heat source, in a draft from an
external door or in direct sunlight. Closed radiator ther-
mostats can also cause problems.
NIBE F1145
4 5 6 7
BT25
AA3-X6
18
BT71
BT71
The heat pump operates without the sensor, but if one
wishes to read off the accommodation's indoor temper-
ature in F1145's display, the sensor must be installed.
Connect the room sensor to X6:3 and X6:4 on the input
board (AA3).
If the sensor is to be used to change the room temperat-
ure in °C and/or to change/stabilise the room temperat-
ure, the sensor must be activated in menu 1.9.4.
If the room sensor is used in a room with underfloor
heating, it should only have an indicatory function, not
control of the room temperature.
AA3-X6
F1145
F1145
RG05
External
Caution
Changes of temperature in accommodation
take time. For example, short time periods in
combination with underfloor heating will not
give a noticeable difference in room temperat-
ure.
Connecting external energy meter
NOTE
Connection of external energy meter requires
version 35 or later on input board (AA3) as well
as "display version" 7113 or later.
Connect the energy meter(s) to terminal X22:1-3 and/or
X23:1-3 on input board (AA3) as illustrated.
AA3-X22/23
Activate the energy meter(s) in menu 5.2.4 and then set
the desired value (energy per pulse) in menu 5.3.21.
2 3 4 5
BT50
1 2 3
AA3-X22/23
F1145
ProduktNamn
External
Externt
Chapter 5 |